WAGO I/O System 750
Device Description 25
750-482/000-001 2AI 4-20mA HART NAMUR NE43
Manual
Version 1.0.2
Table 12: Technical Data – Inputs
Temperature coefficient
< ±0.01 %/K of the largest
measurement/output area
Line break detection
I
meas
< 1.0 mA
Short circuit detection
I
meas
> 23 mA
Underrange
I
meas
< 3.6 mA
Range exceeded
I
meas
> 21 mA
Overvoltage protection
30 V, reverse polarity protected
Diagnostics
Wire break, short circuit, measurement
range overflow, measurement range
underflow
Sensor connection
2-conductor
HART devices per channel
1 device (single-drop, no multi-drop)
HART modems per channel
1 modem (no multiplex)
3.6.5
Connection Type
Table 13: Technical Data – Field Wiring
Wire connection
CAGE CLAMP
®
Cross section
0.08 mm² … 2.5 mm², AWG 28 … 14
Stripped lengths
8 mm … 9 mm / 0.33 in
Table 14: Technical Data – Power Jumper Contacts
Power jumper contacts
Blade/spring contact, self-cleaning
Table 15: Technical Data – Data Contacts
Data contacts
Slide contact, hard gold plated, self-
cleaning