WAGO I/O System 750
Commissioning 69
750-482/000-001 2AI 4-20mA HART NAMUR NE43
Manual
Version 1.0.2
click on
Add...
in the context menu (right mouse button).
Select the device type name for your PROFIBUS master in the dialog which
opens and confirm the selection by clicking
[OK].
The name of your PROFIBUS master will now be added in the tree
structure.
6.
Move the mouse to the device type name of your PROFIBUS master in the
tree structure and select it by clicking with the left mouse button.
Next go to the
Device
menu and click
Offline parameterization
.
On the
FDL parameters
tab of the dialog window which opens enter the
baud rate: “12 MBaud” and click on
Set default values
.
Confirm your entries by clicking
[OK].
7.
Click
Set up connection
on the
Device
menu. The device type name of
your PROFIBUS master will now be changed to italics in the tree structure.
8.
Move the mouse to the device type name of your PROFIBUS master in the
tree structure and click on
Add...
in the context menu (right mouse button).
Select “0750-0333 PROFIBUS/HART Gateway” in the dialog which opens
and confirm the selection by clicking
[OK].
The entry for the PROFIBUS/HART communications DTM will now be
added in the tree structure.
9.
Move the mouse once again to the device type name of your PROFIBUS
master in the tree structure and select it by clicking with the left mouse
button.
Next go to
More functions
on the
Device
menu and click on
Device list
on the sub-menu.
A dialog window with a list of devices will open.
Figure 21: Dialog Window “Device List”
10. Select the device with the address 126 by clicking on it and click [
Set DTM
Tag/Address...]
.
Now, instead of the 126, enter the station address, which is physically set
by the two rotary decade switches (decimal) on your PROFIBUS