22 Device Description
WAGO I/O System 750
750-482/000-001 2AI 4-20mA HART NAMUR NE43
Manual
Version 1.0.2
3.3
Display Elements
Figure 5: Display Elements
Table 8: Legend for Figure “Display Elements“
A
B
Channel 1 state Description
Function
HART 1
Error
HART 1
Green/Off 1 × flashing Power-On
Hardware and software initialization
Green
Red/Off
Ready for
operation
Power-On completed successfully;
local bus communication
Green/Off Red
Error
Wire break, measuring overrange/
underrange
E
F
Channel 2 state Description
Function
HART 2
Error
HART 2
Green/Off 1 × flashing Power-On
Hardware and software initialization
Green
Red/Off
Ready for
operation
Power-On completed successfully;
local bus communication
Green/Off Red
Error
Wire break, measuring overrange/
underrange
3.4
Operating Elements
The I/O module 750-482/000-001 has no operating elements.