212 Appendix
WAGO I/O SYSTEM 750 XTR
750-333/040-000 FC PROFIBUS G2 12MBd XTR
Manual
Version 1.4.0
Table 164: Parameters of the 2-channel analog output modules (AO_PAR)
2AO_PAR
Representatives of the 2AO_PAR:
75x-562, 75x-563
Parameterization data length in bytes
Standard parameterization
Structured parameterization
10
14
Parameter
Settings
Description
Scope
Operating mode
1)
The corresponding output channel works in the
range
Channel
0-10 V
*)
•
0
… 10 V
+/-10 V
•
+/-10 V
Operating mode
2)
The corresponding output channel works in the
range
Channel
0-20 mA
•
0
… 20 mA
4-20 mA
*)
•
4
… 20 mA
6-18 V
•
6
… 18 V
On exceeding user limits
If the limit value in regard to the output data is
exceeded, the output value is
Channel
No limitation of output value
•
not limited.
Limitation of output value
•
limited.
Output
The corresponding output is
Channel
in parameterized operating
mode
*)
•
working in the configured operating mode.
high-impedance
•
high-resistance disabled.
Behavior on K-Bus timeout
With I/O module response monitoring of 100 ms
Channel
0 V output
*)1)
•
outputs the corresponding output 0 V.
output 0 mA respective
6 V
*)2)
•
the corresponding output is set to 0 mA or 6 V
depending on the operating mode.
hold last output value
•
the last output value is output.
output manufacturer substitute
value
•
the manufacturer substitute value is output.
set output to high-impedance
•
the corresponding output is switched to high-
impedance.
Switch-on delay [s]
After switching off the corresponding output by
exceeding the maximum operating temperature,
restart occurs after
Channel
0.10
•
0.1 s
0.20
•
0.2 s
0.30
•
0.3 s
0.50
*)
•
0.5 s
0.75
•
0.75 s
1.00
•
1 s
2.00
•
2 s
Substitute value
0
*)
… 65535
If, in the event of a PROFIBUS DP fault, the
switching of substitute values is enabled by the
fieldbus coupler parameterization, this value is
transmitted to the periphery in the event of a fault.
Channel
*)
Default settings
1)
Applies to 75x-562
2)
Applies to 75x-563