WAGO I/O SYSTEM 750 XTR
Appendix 209
750-333/040-000 FC PROFIBUS G2 12MBd XTR
Manual
Version 1.4.0
The table shows the parameterization properties of the 3-phase power
measurement modules with asynchronous diagnostic properties and individual
parameters.
Table 162: Parameter of the 3-phase power measurement modules (1AI_PAR)
1AI_PAR
Representatives of the 1AI_PAR:
75x-494, 75x-494/000-001,
75x-495, 75x-495/000-001, 75x-495/000-002
Parameterization data length in bytes
Standard parameterization
Structured parameterization
20
1)
(22
2)
)
24
1)
(26
2)
)
Parameter
Settings
Description
Scope
Terminal is physically
The I/O module process data is
Module
(optionally) not plugged
•
(optionally) set to zero by the fieldbus
coupler.
plugged
*)
•
supplied by the I/O module.
Diagnosis
The diagnostic information of the corresponding
channel is
Channel
disabled
*)
•
not transmitted to the PROFIBUS DP
master.
enabled
•
transmitted to the PROFIBUS DP master.
K-Bus Monitoring
If no process data is received for 100 ms, the
watchdog of the I/O module triggers
Module
deactivated
*)
•
not.
activated
•
yes.
DC Measurement
Measurement DC measured values
Module
deactivated
*)
•
not possible.
activated
•
possible.
Network frequency
The network frequency is
Module
50 Hz
*)
•
50 Hz
60 Hz
•
60 Hz
Phase for peak value
The phase for determining of the peak value is
Module
L1
*)
•
L1
L2
•
L2
L3
•
L3
Scaling factor energy values
The scaling factor of the energy values is
Module
1 mWh
3)*)
•
1 mWh
0,01 Wh
3)
•
10 mWh
0,1 Wh
3)
•
100 mWh
1 Wh
3)
•
1 Wh
0,01 kWh
3)
•
10 Wh
0,1 kWh
3)
•
100 Wh
1 kWh
3)
•
1 kWh
5 mWh
4)*)
•
5 mWh
0,05 Wh
4)
•
50 mWh
0,5 Wh
4)
•
500 mWh
5 Wh
4)
•
5 Wh
0,05 kWh
4)
•
50 Wh
0,5 kWh
4)
•
500 Wh
5 kWh
4)
•
5 kWh
Storing interval energy
consumption [s]
The sensor is connected with
Module
60
1)
… 255
•
60 s
… 255 s
Detection Rogowski coils
5)
There are Rogowski coils used type
Module
RT500
*)
•
RT500
RT2000
•
RT2000
Auto Reset Min-/Max values
The minimum and maximum current, voltage,
power and frequency values
Channel
deactivated
•
not automatically deleted.
activated
•
automatically deleted.
User-defined scaling
The User-defined scaling is
Channel
deactivated
•
inactive.
activated
•
active.