WAGO I/O SYSTEM 750 XTR
Appendix 221
750-333/040-000 FC PROFIBUS G2 12MBd XTR
Manual
Version 1.4.0
Table 177: Parameters of the PROFIsafe V2 I/O modules (PSAFE_V2)
PSAFE_V2
Representative of the PSAFE_V2:
753-662/000-002, 753-667/000-002,
75x-661/000-003, 75x-662/000-003,
75x-666/000-003, 75x-667/000-003
Parameterization data length in bytes
Standard parameterization
Structured parameterization
17
21
Parameter
Settings
Description
Scope
Terminal is physically
The I/O module process data is
Module
(optionally) not plugged
•
(optionally) set to zero or filtered by the
fieldbus coupler.
plugged
*)
•
supplied by the I/O module or output to the
periphery.
Diagnosis
The diagnostic information of the corresponding
channel is
Channel
disabled
*)
•
not transmitted to the PROFIBUS DP master.
enabled
•
transmitted to the PROFIBUS DP master.
F_Check_SeqNr
In the CRC calculation, the sequence number is
Module
Check
•
included.
NoCheck
*)
•
not included.
F_Check_iPar
Individual Parameters in the F parameter field
Module
NoCheck
*)
•
are not checked.
F_SIL
The safety requirement level is
Module
SIL3
*)
•
SIL3.
F_CRC_Length
The F_CRC has a length of
Module
2-Byte-CRC
•
2 byte.
3-Byte-CRC
*)
•
3 byte.
F_Block_ID
The ID of the F parameter field is
Module
0
*)
•
0
F_Par_Version
The PROFIsafe layer is operated in
Module
V1-mode
•
PROFIsafe V1 mode.
V2-mode
*)
•
PROFIsafe V2 mode.
F_Source_Add
The F source address can accept the following
values:
Module
1 ... 65534
•
1
… 65534
F_Dest_Add
The F destination address can accept the
following values:
Module
1
… 65534
•
1
… 65534
F_WD_Time
The F monitoring time can accept the following
values:
Module
50
… 150
*)
… 10000
•
50
… 10000 ms
*)
Default settings