WAGO I/O SYSTEM 750 XTR
Appendix 151
750-333/040-000 FC PROFIBUS G2 12MBd XTR
Manual
Version 1.4.0
12.2.5
Analog Input Modules
The PI configurations of the analog input modules are divided into the following
module types:
Table 100: Analog Input Modules
– Module Types
PBDP module type
Description
Proxy I/O modules
2AI(_PAR)
2-Channel Analog Input Modules, channel diagnostics
16 bit input data, opt. HART profile via PROFIBUS
75x-452, 75x-454, 75x-456, 75x-461,
75x-462, 75x-465, 75x-466, 75x-467,
75x-469, 75x-470, 75x-472, 75x-473,
75x-474, 75x-475, 75x-476, 75x-477,
75x-478, 75x-479, 75x-480, 750-481,
75x-482, 75x-483, 750-484, 750-485,
750-487, 75x-491, 75x-492
2AI_RA(_PAR)
2-
Channel Analog Input Modules
, channel diagnostics
16 bit input and output data plus
control and status byte per signal channel,
Access to the register structure via cyclic
data exchange, opt. HART profile via PROFIBUS
75x-452, 75x-454, 75x-456, 75x-461,
75x-462, 75x-465, 75x-466, 75x-467,
75x-469, 75x-470, 75x-472, 75x-473,
75x-474, 75x-475, 75x-476, 75x-477,
75x-478, 75x-479, 75x-480, 750-481,
75x-482, 75x-483, 750-484, 750-485,
750-487,75x-491, 75x-492
2AI_2HV
2-Channel Analog Input Modules, HART, channel
diagnostics, 16 bit input data plus a 32 bit HART variable
per signal channel
75x-482, 750-484
2AI_4HV
2-Channel Analog Input Modules, HART, channel
diagnostics, 16 bit input data plus two 32 bit HART
variables per signal channel
75x-482, 750-484
2AI_6HV
2-Channel Analog Input Modules, HART, channel
diagnostics, 16 bit input data plus three 32 bit HART
variables per signal channel
75x-482, 750-484
2AI_8HV
2-Channel Analog Input Modules, HART, channel
diagnostics, 16 bit input data plus four 32 bit HART
variables per signal channel
75x-482, 750-484
3AI_RA
3-Channel Analog Input Modules, channel diagnostics
16 bit input and output data plus
control and status byte per signal channel,
access to the register structure via cyclic data exchange
75x-493
4AI(_PAR)
4-Channel Analog Input Modules, channel diagnostics,
16 bit input data per signal channel
750-450, 75x-453, 75x-455, 75x-457,
75x-459, 75x-460, 75x-463, 75x-464,
75x-468
4AI_RA(_PAR)
4-Channel Analog Input Modules, channel diagnostics,
16 bit input and output data plus
control and status byte per signal channel,
access to the register structure via cyclic data exchange
750-450, 75x-453, 75x-455, 75x-457,
75x-459, 75x-460, 75x-463, 75x-464,
75x-468
8AI_PAR
8 Channel Analog Input Modules, 16 bit Input data per
signal channel
750-451
8AI_RA_PAR
8 Channel Analog Input Modules, channel diagnostics,
16 bit input and output data plus
control and status byte per signal channel,
access to the register structure via cyclic data exchange
750-451
3PLM_PAR
3-Phase Power Measurement Modules,
16/32 bits data composition
75x-494, 75x-495
Analog input modules pass the digitalized process value of the input channels
and optional channel diagnostic information to the DP master in each status byte.
For I/O modules with HART interface, up to four HART variables can be
transmitted as an option in addition to the input process values.
The following table lists the number of bytes reserved for the individual module in
the respective process image (PI).