190 Appendix
WAGO I/O SYSTEM 750 XTR
750-333/040-000 FC PROFIBUS G2 12MBd XTR
Manual
Version 1.4.0
The following table describes the process image information of the individual
module types for the PROFIsafe modules.
Table 135: PROFIsafe modules
– Process image information
PBDP module type
PI
Offset
[Byte]
Bit/byte allocation
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
P_SAFE,
P_SAFE_iPar
I
0
I7
1)
I6
1)
I5
1)
I4
1)
I3
I2
I1
I0
1
F-Status
2
F-Device-CRC
2)
Byte 2
Consecutive number
3)
F-Device
3
F-Device-CRC
Byte 1
4
F-Device-CRC
Byte 0
O
0
RES
RES
RES
RES
O3
4)
O2
4)
O1
4)
O0
4)
1
F-Control
2
F-Host-CRC
2)
Byte 2
Consecutive number
3)
F-Host
3
F-Host-CRC
Byte 1
4
F-Host-CRC
Byte 0
1)
Only available with 8-Channel F-Input modules
2)
In PROFIsafe V2 mode
3)
In PROFIsafe V1 mode
4)
Only available with 4-Channel F-Output module