WAGO I/O SYSTEM 750 XTR
Commissioning
87
750-333/040-000 FC PROFIBUS G2 12MBd XTR
Manual
Version 1.4.0
Table 38: Table Modules
Module
Description
Example
Module
Identifier byte according to the general
identifier format for digital input or output I/O
modules:
One or two bytes are allocated in the
respective process image. The information of
the digital inputs and/or outputs of the
respective I/O module are mapped to the least
significant bits.
Identifier byte according to the general
identifier format for analog input or output I/O
modules:
Only the user data required for operating the
I/O module are mapped in the respective
process image area (input process image
and/or output process image).
75x-400 2 DI/24 V DC/3.0 ms
75x-461 2 AI/RTD
75x-550 2 AO/0-10 V
*-Module
Identifier byte according to the special
identifier format for digital input or output I/O
modules:
A byte previously allocated with “module” that
is not completely occupied with digital
information subsequent to configured
“*-modules” is populated with the information
of the digital inputs and/or outputs for the
respective I/O module .
A requirement is that all information of the
respective I/O module can be accommodated
in the byte that's already allocated.
*75x-400 2 DI/24 V DC/3.0 ms
RA module
Identifier byte according to the special
identifier format for complex modules,
particularly for analog inputs and outputs:
Input and output information including control
and status byte are mapped in the respective
process image area. This way, the register
structure of the respective I/O modules can be
accessed when parameterization is done via
cyclic process data exchange.
75x-461 2 AI/RTD RA
75x-550 2 AO/0-10 V RA