2.1 BEFORE SWITCHING ON

Before switching the appliance on, please familiarise yourself 
with:
-  how to isolate the appliance from the gas, water, and electricity 

supplies;

-  how to check and top-up – if necessary – the system water 

pressure;

-  the time clock or programmer (if fitted);

-  any external thermostats and their functions;
-  the appliance controls.

2.2 APPLIANCE CONTROLS (see fig. 1)

The appliance controls are situated on the lower front of the 
appliance. The appliance controls include:
- pressure gauge;
- appliance mode selector;
- temperature selector;
- burner ON mode (green);
- fault indicator (red);
- servicing mode indicator (yellow)

NOTE

The appliance frost protection is active in all the boiler modes.
The temperature selector can be used to vary the temperature 
of the water that circulates around your radiators.

The temperature range is adjustable between 40°C and 80°C.

When the status indicator (Green) is lit it indicates that the flame 

is present and the burner is ON.

When the fault indicator (Red) is lit it indicates that the appliance 

has identified a possible fault and performed a safety lockout.

When the fault indicator (Yellow) is lit it indicates that there is 
a Servicing operation in progress.

2.3 LIGHTING THE BOILER

Ensure the gas and electrical supply to the boiler are 
turned on.

Turn the mode selector switch to the 

ON

 position.  When there 

is a request for heating or hot water via the time clock or pro-
grammer, the boiler will begin an ignition sequence.  When the 
appliance reaches the CH set temperature, the burner will go 
off for a minimum period of approximately 3 minutes.
When the programmer/time clock or external thermostats 

heating request has been satisfied, the appliance will switch 

off automatically.

2.4 ADJUSTING THE HEATING TEMPERATURE

Rotate the temperature selector – clockwise to increase, counter-

clockwise to decrease – to the desired temperature setting.  The 
temperature can be set from a minimum of 40°C to a maximum 
of 80°C (if standard CH mode is selected).

2.5 EXPLANATION OF FEATURES

Although the Vokèra Vibe has been designed for simplicity of 
use, it utilises the latest in boiler technology, enabling a host 
of functions to be carried out simultaneously.

2.6 AUTOMATIC TEMPERATURE CONTROL

The automatic temperature control function (SARA), permits 

the boiler (when the heating temperature selector is set within 
4 and 6 sector) to automatically adjust (raise) the heating. 
The activation and the disable of the function is visualized by 
blinking the green led.

2. GETTING STARTED

3.1  HOW TO TOP-UP THE SYSTEM PRESSURE 

(fig. 1-2)

The system pressure must be checked periodically to ensure the 
correct operation of the boiler. The needle on the gauge should 

be reading between 1 and 1.5 BAR when the boiler is in an off 

position and has cooled to room temperature. If the pressure 
requires ‘topping-up’ use the following instructions as a guide.

-  Locate  the  filling  valve  connections  (usually  beneath  the 

boiler, see fig. 2).

-  Attach the filling loop to both connections.

-  Open the filling valve slowly until you hear water entering the 

system.

-  Close the filling valve when the pressure gauge (on the boiler) 

reads between 1 and 1.5 BAR (see fig. 1).

-  Remove the filling loop from the connections.

3.2 HOW TO RESET THE APPLIANCE

When the red fault LED is illuminated, the appliance will require 
to be reset manually. Before resetting the boiler, check what 
action is required to be taken, using the information on the 
fault code table below. Allow a period of two minutes to elapse 
before rotate the mode selector knob across the 

 position 

(see fig. 1).

IMPORTANT

If the appliance requires to be reset frequently, it may be indica-
tive of a fault, please contact your installer or Vokèra Customer 
Services for further advice.

3. HOW TO...

Fig. 2

control 

valve

temporary 

connection

control 

valve

supply pipe

double 

check valve

flow/return 

pipe

3.3 HOW TO SHUT DOWN THE SYSTEM FOR 
SHORT PERIODS

The system and boiler can be shut down for short periods by 
simply turning the time clock to the off position. It is also advis-
able to turn off the main water supply to the house.

3.4 HOW TO SHUT DOWN THE SYSTEM FOR 
LONG PERIODS 

If the house is to be left unoccupied for any length of time – 
especially during the winter – the system should be thoroughly 
drained of all water. The gas, water, and electricity supply to 
the house should also be turned off. For more detailed advice 
contact your installer.

3.5 HOW TO CARE FOR THE APPLIANCE 

To clean the outer casing use only a clean damp cloth. Do not 
use any scourers or abrasive cleaners.

Содержание Vibe 20 A G.C. N 41-094-84

Страница 1: ...NS TO BE RETAINED BY USER Vok ra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic hot water systems in the UK Vibe High ef...

Страница 2: ...8 Mounting on a combustible surface 11 3A 9 Timber framed buildings 11 3A 10 Inhibitors 11 3A 11 Declaration of conformity 11 Installation Page 4 1 Delivery 12 4 2 Contents 12 4 3 Unpacking 12 4 4 Pr...

Страница 3: ...er has been designed to meet and exceed the very latest standards in gas central heating technology and if cared for will give years of reliable use and efficiency Please therefore take some time to r...

Страница 4: ...ating temperature selector move the selector clockwise to increase the heating outlet temperature or counter clockwise to reduce the tem perature range 40 C 80 C for standard central heating The autom...

Страница 5: ...t simultaneously 2 6 AUTOMATIC TEMPERATURE CONTROL The automatic temperature control function SARA permits the boiler when the heating temperature selector is set within 4 and 6 sector to automaticall...

Страница 6: ...I NEED TO CALL AN ENGINEER Ifyouthinkyourboilermayhavedevelopedafault pleasecontact yourinstallerorVok raCustomerServices 08443910999 UK or 056 7755057 ROI have all your details to hand including ful...

Страница 7: ...e ap plications These appliances are designed for use with a sealed system only consequently they are not intended for use on open vented systems This booklet is an integral part of the appliance It i...

Страница 8: ...bytheelectroniccircuittoensureflamestability at the burner Once successful ignition has been achieved the electronic circuitry increases the gas rate to 75 for a period of 15minutes Thereafter theboil...

Страница 9: ...Dry weight kg 26 28 2 5 Clearances Vibe 20A Vibe 25A Sides 12mm Top 150mm from casing or 25mm above flue elbow whichever is applicable Bottom 150mm Front 600mm 2 6 Connections Vibe 20A Vibe 25A Flow...

Страница 10: ...wall 300 mm P From a structure to the side of the vertical terminal 300 mm Q From the top of the vertical terminal to the roof flashing As determined by the fixed collar of the vertical terminal R To...

Страница 11: ...an unusually high water content it may be necessary to provide additional expansion capacity see 6 18 3 6 6 FILLING POINT A method for initial filling of the system and replacing water lost during ser...

Страница 12: ...is no requirement for a sheet of fireproof material to protect the wall 3 9 TIMBER FRAMED BUILDINGS If the appliance is to be fitted in a timber framed building it shouldbefittedinaccordancewiththeIns...

Страница 13: ...omplies with the local water authority regulations 3A 6 7 LOW PRESSURE SEALED SYSTEM An alternative method of filling the system would be from an independent make up vessel or tank mounted in a positi...

Страница 14: ...e see 2 9 Areduction must also be made to the maximum length see table below when additional bends are used Reduction for additional bends Bend Reduction in maximum flue length for each bend 45 bend 1...

Страница 15: ...ING THE REAR FLUE fig 14 rear flue outlet only Using the template provided mark and drill a 125mm hole for the passage of the flue pipe The hole should be drilled LEVEL to ensure any condense fluid th...

Страница 16: ...rminal 1 0 metre 359 Twin adapter kit N A 531 Pitched roof flashing plate N A 532 Flat roof flashing plate N A 0225815 Condensate drain kit N A 0225820 0 25m extension pair 50mm 0225825 0 5m extension...

Страница 17: ...iance flue outlet Remove the blanking plate located to the left of the appliance flue outlet and using the same screws install the air inlet plate B Using the hole in the exhaust connection manifold a...

Страница 18: ...e wire to NEUTRAL supply green yellow to EARTH connection Insertthesupplied3 AMPfuseintothefusedisolatororfusedplug Should the fly lead be unsuitable refer to 4 7 3 for details on how to connect the e...

Страница 19: ...nce service valves are open 5 6 INITIAL LIGHTING Ensure the electrical supply to the appliance is switched on Ensure any external controls are switched to an ON position and are calling for heat Move...

Страница 20: ...ilure to install and com mission the appliance to the manufacturers instructions will invalidate the warranty 5 13 INSTRUCTING THE USER Hand over all documentation supplied with this appliance includi...

Страница 21: ...from the pump assembly and remove the AAV assembly J Replace in the reverse order 6 7 1 TOP AUTOMATIC AIR RELEASE VALVE fig 29 Carry out component removal procedure as described in 6 4 Remove the AAV...

Страница 22: ...tly ease the fan assembly out of its location Once the assembly has been removed the burner K1 can be withdrawn from the heat engine Ensure the seals L1 is in good condition taking care to ensure it i...

Страница 23: ...s described in 6 4 Remove the locking pin Q1 that secures the cover R1 to the hydraulic manifold Using a hooked piece of wire carefully withdraw the by pass cartridge S1 Ensure all seals are in good c...

Страница 24: ...the ignition sequence com mences Ignition is sensed by the electronic circuit to ensure flame stability at the burner Once successful ignition has been achieved the electronic circuitry increases the...

Страница 25: ...it the plug fig 40 L2 and move the mode selector through position Remove the test probe from the test point and refit the sealing screw s and or cap IMPORTANT A GAS TIGHTNESS CHECK MUST BE CARRIED OUT...

Страница 26: ...as failed but no fault is in dicated a detailed continuity check will be required to trace the fault A visual inspection of components may also assist in locating the fault 7 7 3 POLARITY CHECK With t...

Страница 27: ...LICATIONS The appliance can be used with the following controls twin channel programmers The appliance can be used in conjunction with typical S Plan systems and Y Plan systems Please contact Vokera t...

Страница 28: ...sed JP5 Selection operating only heating JP6 Unused JP7 Unused JP8 Closed Unused LED Led 1 green working status or temporary stop Led 2 yellow CO 2 function ON Led 3 red boiler lock out brown CN3 blue...

Страница 29: ...INSTALLATION The entire installation including the meter must be purged and checked for gas tightness 9 6 2 GAS VALVE MAXIMUM SETTING Set the CO button at maximum see 10 3 1 once the maximum is obtai...

Страница 30: ...TO MINIMUM RATE In accordance with section 7 3 set boiler to operate at minimum rate to minimum load condition Allow sufficient time for combustion to stabilise YES Is CO 350ppm and CO CO2 ratio less...

Страница 31: ...commissioning checklist completed in full To instigate the boiler guarantee the boiler needs to be registered with the manufacturer within one month of the installation To maintain the boiler guarante...

Страница 32: ...nterlock Provided ALL SYSTEMS The system has been flushed and cleaned in accordance with BS7593 and boiler manufacturer s instructions Yes What system cleaner was used What inhibitor was used Quantity...

Страница 33: ...egister No Record At max rate CO ppm AND CO At min rate Where Possible CO ppm AND CO Comments Signature SERVICE 04 Date Engineer name Company name Telephone No Gas safe register No Record At max rate...

Страница 34: ...33...

Страница 35: ...34...

Страница 36: ...1HG enquiries vokera co uk www vokera co uk www vokera ie Sales General Enquires T 0844 391 0999 F 0844 391 0998 Vok ra Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limite...

Отзывы: