background image

11

the terminal must be protected by a guard of durable material. 

The guard must be fitted centrally over the terminal.  Refer to 

I.S. 813, when the terminal is 0.5 metres (or less) below plastic 
guttering or 1 metre (or less) below painted eaves.

3A.5 AIR SUPPLY

The following notes are intended for general guidance only.

This appliance is a room-sealed, fan-flued boiler, consequently it 

does not require a permanent air vent for combustion air supply.
When installed in a cupboard or compartment, ventilation for 
cooling purposes is also not required.

3A.6 WATER CIRCULATION

Specific recommendations are given in I.S. 813.  The following 

notes are for general guidance only.

3A.6.1 PIPEWORK

It is recommended that copper tubing be used in conjunction 
with soldered capillary joints.
Where possible pipes should have a gradient to ensure air 

is carried naturally to air release points and that water flows 

naturally to drain cocks.
Except where providing useful heat, pipes should be insulated 
to avoid heat loss and in particular to avoid the possibility of 
freezing. Particular attention should be paid to pipes passing 

through ventilated areas such as under floors, loft space and 

void areas.

3A.6.2 AUTOMATIC BY-PASS

The appliance has a built-in automatic by-pass, consequently 
there is no requirement for an external by-pass, however the 
design of the system should be such that it prevents boiler 
‘cycling’.

3A.6.3 DRAIN COCKS

These must be located in accessible positions to facilitate 
draining of the appliance and all water pipes connected to the 
appliance.

3A.6.4 AIR RELEASE POINTS

These must be positioned at the highest points in the system 
where air is likely to be trapped. They should be used to expel 

trapped air and allow complete filling of the system.

3A.6.5 EXPANSION VESSEL

The appliance has an integral expansion vessel to accom-
modate the increased volume of water when the system is 
heated. It can accept up to 8 litres of expansion from within 

the system, generally this is sufficient, however if the system 

has an unusually high water content, it may be necessary to 
provide additional expansion capacity (see 6.18).

3A.6.6 FILLING POINT

A method for initial filling of the system and replacing water lost 

during servicing etc. is provided (see fig. 7). You should ensure 

this method of filling complies with the local water authority 

regulations. 

3A.6.7 LOW PRESSURE SEALED SYSTEM

An alternative method of filling the system would be from an 

independent make-up vessel or tank mounted in a position 
at least 1 metre above the highest point in the system and at 

least 5 metres above the boiler (see fig. 8). The cold feed from 

the make-up vessel or tank must be fitted with an approved 

non-return valve and stopcock for isolation purposes. The feed 
pipe should be connected to the return pipe as close to the 
boiler as possible.

3A.6.8 FREQUENT FILLING

Frequent  filling  or  venting  of  the  system  may  be  indicative 

of a leak. Care should be taken during the installation of the 
appliance to ensure all aspects of the system are capable of 
withstanding pressures up to at least 3 bar.

3A.7 ELECTRICAL SUPPLY

The appliance is supplied for operation on 230V @ 50Hz electri-
cal supply; it must be protected with a 3-amp fuse. The method 

of connection to the mains electricity supply must allow for 
complete isolation from the supply. The preferred method is by 
using a double-pole switch fuse spur with a contact separation 
of at least 3,5 mm (3° high-voltage category). The switch must 
only supply the appliance and its corresponding controls, i.e. 
time clock, room thermostat, etc. 

3A.8 MOUNTING ON A COMBUSTIBLE

 

SURFACE

If the appliance is to be fitted on a wall of combustible mate

-

rial, there is no requirement for a sheet of fireproof material to 

protect the wall.

3A.9 TIMBER FRAMED BUILDINGS

If the appliance is to be fitted in a timber framed building, it 

should be fitted in accordance with I.S. 813 and local Building 

Regulations.

The Institute of Gas Engineers publication (IGE/UP/7) ‘Guide 

for Gas Installations in Timber Frame Buildings’ gives specific 

advice on this type of installation.
 

3A.10 INHIBITORS

Vokèra recommend that an inhibitor - suitable for use with 
aluminium heat exchangers - is used to protect the boiler and 
system from the effects of corrosion and/or electrolytic action. 
The inhibitor must be administered in strict accordance with 
the manufacturers instructions*.
*Water treatment of the complete heating system - including 
the boiler - should be carried out in accordance with I.S. 813 
and the Domestic Water Treatment Association’s (DWTA) code 
of practice.

3A.11 DECLARATION OF CONFORMITY

A Declaration of Conformity (as defined in I.S. 813) must be 

provided on completion of the installation. 
A copy of the declaration must be given to the responsible 
person and also to the gas supplier if required.

Содержание Vibe 20 A G.C. N 41-094-84

Страница 1: ...NS TO BE RETAINED BY USER Vok ra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic hot water systems in the UK Vibe High ef...

Страница 2: ...8 Mounting on a combustible surface 11 3A 9 Timber framed buildings 11 3A 10 Inhibitors 11 3A 11 Declaration of conformity 11 Installation Page 4 1 Delivery 12 4 2 Contents 12 4 3 Unpacking 12 4 4 Pr...

Страница 3: ...er has been designed to meet and exceed the very latest standards in gas central heating technology and if cared for will give years of reliable use and efficiency Please therefore take some time to r...

Страница 4: ...ating temperature selector move the selector clockwise to increase the heating outlet temperature or counter clockwise to reduce the tem perature range 40 C 80 C for standard central heating The autom...

Страница 5: ...t simultaneously 2 6 AUTOMATIC TEMPERATURE CONTROL The automatic temperature control function SARA permits the boiler when the heating temperature selector is set within 4 and 6 sector to automaticall...

Страница 6: ...I NEED TO CALL AN ENGINEER Ifyouthinkyourboilermayhavedevelopedafault pleasecontact yourinstallerorVok raCustomerServices 08443910999 UK or 056 7755057 ROI have all your details to hand including ful...

Страница 7: ...e ap plications These appliances are designed for use with a sealed system only consequently they are not intended for use on open vented systems This booklet is an integral part of the appliance It i...

Страница 8: ...bytheelectroniccircuittoensureflamestability at the burner Once successful ignition has been achieved the electronic circuitry increases the gas rate to 75 for a period of 15minutes Thereafter theboil...

Страница 9: ...Dry weight kg 26 28 2 5 Clearances Vibe 20A Vibe 25A Sides 12mm Top 150mm from casing or 25mm above flue elbow whichever is applicable Bottom 150mm Front 600mm 2 6 Connections Vibe 20A Vibe 25A Flow...

Страница 10: ...wall 300 mm P From a structure to the side of the vertical terminal 300 mm Q From the top of the vertical terminal to the roof flashing As determined by the fixed collar of the vertical terminal R To...

Страница 11: ...an unusually high water content it may be necessary to provide additional expansion capacity see 6 18 3 6 6 FILLING POINT A method for initial filling of the system and replacing water lost during ser...

Страница 12: ...is no requirement for a sheet of fireproof material to protect the wall 3 9 TIMBER FRAMED BUILDINGS If the appliance is to be fitted in a timber framed building it shouldbefittedinaccordancewiththeIns...

Страница 13: ...omplies with the local water authority regulations 3A 6 7 LOW PRESSURE SEALED SYSTEM An alternative method of filling the system would be from an independent make up vessel or tank mounted in a positi...

Страница 14: ...e see 2 9 Areduction must also be made to the maximum length see table below when additional bends are used Reduction for additional bends Bend Reduction in maximum flue length for each bend 45 bend 1...

Страница 15: ...ING THE REAR FLUE fig 14 rear flue outlet only Using the template provided mark and drill a 125mm hole for the passage of the flue pipe The hole should be drilled LEVEL to ensure any condense fluid th...

Страница 16: ...rminal 1 0 metre 359 Twin adapter kit N A 531 Pitched roof flashing plate N A 532 Flat roof flashing plate N A 0225815 Condensate drain kit N A 0225820 0 25m extension pair 50mm 0225825 0 5m extension...

Страница 17: ...iance flue outlet Remove the blanking plate located to the left of the appliance flue outlet and using the same screws install the air inlet plate B Using the hole in the exhaust connection manifold a...

Страница 18: ...e wire to NEUTRAL supply green yellow to EARTH connection Insertthesupplied3 AMPfuseintothefusedisolatororfusedplug Should the fly lead be unsuitable refer to 4 7 3 for details on how to connect the e...

Страница 19: ...nce service valves are open 5 6 INITIAL LIGHTING Ensure the electrical supply to the appliance is switched on Ensure any external controls are switched to an ON position and are calling for heat Move...

Страница 20: ...ilure to install and com mission the appliance to the manufacturers instructions will invalidate the warranty 5 13 INSTRUCTING THE USER Hand over all documentation supplied with this appliance includi...

Страница 21: ...from the pump assembly and remove the AAV assembly J Replace in the reverse order 6 7 1 TOP AUTOMATIC AIR RELEASE VALVE fig 29 Carry out component removal procedure as described in 6 4 Remove the AAV...

Страница 22: ...tly ease the fan assembly out of its location Once the assembly has been removed the burner K1 can be withdrawn from the heat engine Ensure the seals L1 is in good condition taking care to ensure it i...

Страница 23: ...s described in 6 4 Remove the locking pin Q1 that secures the cover R1 to the hydraulic manifold Using a hooked piece of wire carefully withdraw the by pass cartridge S1 Ensure all seals are in good c...

Страница 24: ...the ignition sequence com mences Ignition is sensed by the electronic circuit to ensure flame stability at the burner Once successful ignition has been achieved the electronic circuitry increases the...

Страница 25: ...it the plug fig 40 L2 and move the mode selector through position Remove the test probe from the test point and refit the sealing screw s and or cap IMPORTANT A GAS TIGHTNESS CHECK MUST BE CARRIED OUT...

Страница 26: ...as failed but no fault is in dicated a detailed continuity check will be required to trace the fault A visual inspection of components may also assist in locating the fault 7 7 3 POLARITY CHECK With t...

Страница 27: ...LICATIONS The appliance can be used with the following controls twin channel programmers The appliance can be used in conjunction with typical S Plan systems and Y Plan systems Please contact Vokera t...

Страница 28: ...sed JP5 Selection operating only heating JP6 Unused JP7 Unused JP8 Closed Unused LED Led 1 green working status or temporary stop Led 2 yellow CO 2 function ON Led 3 red boiler lock out brown CN3 blue...

Страница 29: ...INSTALLATION The entire installation including the meter must be purged and checked for gas tightness 9 6 2 GAS VALVE MAXIMUM SETTING Set the CO button at maximum see 10 3 1 once the maximum is obtai...

Страница 30: ...TO MINIMUM RATE In accordance with section 7 3 set boiler to operate at minimum rate to minimum load condition Allow sufficient time for combustion to stabilise YES Is CO 350ppm and CO CO2 ratio less...

Страница 31: ...commissioning checklist completed in full To instigate the boiler guarantee the boiler needs to be registered with the manufacturer within one month of the installation To maintain the boiler guarante...

Страница 32: ...nterlock Provided ALL SYSTEMS The system has been flushed and cleaned in accordance with BS7593 and boiler manufacturer s instructions Yes What system cleaner was used What inhibitor was used Quantity...

Страница 33: ...egister No Record At max rate CO ppm AND CO At min rate Where Possible CO ppm AND CO Comments Signature SERVICE 04 Date Engineer name Company name Telephone No Gas safe register No Record At max rate...

Страница 34: ...33...

Страница 35: ...34...

Страница 36: ...1HG enquiries vokera co uk www vokera co uk www vokera ie Sales General Enquires T 0844 391 0999 F 0844 391 0998 Vok ra Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limite...

Отзывы: