background image

17

4.6 CONNECTING THE GAS AND WATER

The appliance is supplied with an accessory pack that includes 
service valves, sealing washers’ etc, for use with the service 
valves.

4.6.1 GAS (

fi

 g. 22)

The appliance is supplied with a 15mm service valve, connect 
a 15mm pipe to the inlet of the valve and tighten both nuts.

NOTE

It will be necessary to calculate the diameter of the gas supply 
pipe to ensure the appliance has an adequate supply of gas.

4.6.2 FLOW & RETURN (

fi

 g. 22)

The appliance is supplied with 22mm service valves for the 
fl ow and return connections, connect a 22mm pipe to the inlet 
of each valve and tighten both nuts.

NOTE

Depending on system requirements, it may necessary to in-
crease the size of the fl ow & return pipe work after the service 
valve connections. 

4.6.3 SAFETY VALVE (

fi

 g. 22)

Connect the safety valve connection pipe to the safety valve 
outlet. Connect a discharge pipe to the other end of the safety 
valve connection pipe and tighten. The discharge pipe must 
have a continuous fall away from the appliance to outside and 
allow any water to drain away thereby eliminating the possibil-
ity of freezing. The discharge pipe must terminate in a position 
where any water – possibly boiling – discharges safely without 
causing damage or injury, but is still visible.

4.6.4 CONDENSE PIPE

During normal operation the boiler produces condense which 
is collected in a trap located in the lower part of the boiler. A 
fl exible pipe (condense outlet pipe) is connected to the outlet 
of the trap. The fl exible pipe must be connected to a plastic 
waste pipe only. The plastic waste pipe must have a minimum 
of a 3º fall towards the drain. Any external run of pipe should 
be insulated to prevent the risk of freezing.  

4.6.5 CONNECTING THE CONDENSATE OUTLET

Gently pull the condense outlet pipe down from its location 
inside the boiler until approximately 100mm protrudes from the 
underside of the boiler, care should be taken to ensure that the 
pipe connection to the trap remains secure. Connect a suitable 
plastic (not copper) pipe (no less than 21mm diameter) to the 
outlet pipe and ensure it discharges in accordance with local 
building regulations or other rules in force.

Fig. 22

4.7 ELECTRICAL CONNECTIONS

The boiler is supplied with a 2-metre fl y-lead. This lead can be 
used for connection to the electrical supply. Connect the fl y-lead 
to a fused plug or fused isolator in the following way:
•  brown wire to LIVE supply
•  blue wire to NEUTRAL supply
•  green/yellow to EARTH connection.

Insert the supplied 3-AMP fuse into the fused isolator or fused plug. 
Should the fl y-lead be unsuitable, refer to 4.7.3 for details on 
how to connect the electrical supply directly to the boiler. 
The electrical supply must be as specifi ed in section 3/3A. A 
qualifi ed electrician should connect the appliance to the electrical 
supply. If controls - external to the appliance - are required, a 
competent person must undertake the design of any external 
electrical circuits, please refer to section 8 for detailed instruc-
tions. ANY EXTERNAL CONTROL OR WIRING MUST BE 
SERVED FROM THE SAME ISOLATOR AS THAT OF THE 
APPLIANCE. The supply cable from the isolator to the appliance 
must be 3-core fl exible sized 0.75mm to BS 6500 or equivalent. 
Wiring to the appliance must be rated for operation in contact 
with surfaces up to 90 ºC.

4.7.1 CASING REMOVAL (

fi

 g. 23)

To gain internal access to the appliance you must fi rst remove 
the casing, proceed as outlined below:
•  locate and unscrew the 2-screws (A) that secure the outer 

casing to the appliance

•  lift the casing upward to disengage it from the top locating 

hooks and then remove

•  store the casing and screws safely until required. Re-fi t  in 

the reverse order

•  remove the retaining screw below the control fascia and 

gently lower it until it rests.

4.7.2 APPLIANCE TERMINAL BLOCK

The appliance terminal block is located on the rear of the control 
fascia. Remove the casing as described in 4.7.1. Gently pull 
the control panel forwards and down. Locate the terminal block 
cover (fi g. 24).

NOTE

The appliance comes with a factory fi tted link (‘TA’) to allow 
basic operation of the boiler via the mode selector switch. If it is 
anticipated that external controls will be required please refer to 
the wiring diagrams in section 8 for more detailed information.

4.7.3 CONNECTING THE MAINS (230V) INPUT 

Unhook and remove the terminal block cover (230V). Pass the 
cable through the cable anchorage point. Connect the supply 
cable wires (LIVE, NEUTRAL, & EARTH) to their corresponding 
terminals (L, N, & E) on the appliance – high voltage – terminal 
block. When connecting the EARTH wire, ensure that it’s left 
slightly longer that the others, this will prevent strain on the 
EARTH wire should the cable become taut. 

The securing screw on the cable anchorage should now be 
tightened. This must be done before the terminal block cover 
is re-fi tted in its position.  

NOTE

It is the installer’s responsibility to ensure that the appliance is 
properly Earthed. Vokèra Ltd. cannot be held responsible for any 
damages or injuries caused as a result of incorrect Earth wiring.

Fig. 23 

A

Fig. 24

Gas 

cock

C/H fl ow 

valve

C/H return 

valve

Safety valve outlet

Содержание Mynute i20

Страница 1: ...is a licensed member of the Benchmark scheme which aims to improve the standards of installation and which aims to improve the standards of installation and commissioning of domestic hot water system...

Страница 2: ...Mounting on a combustible surface 12 3A 9 Timber framed buildings 12 3A 10 Inhibitors 12 3A 11 Declaration of conformity 12 Installation Page 4 1 Delivery 13 4 2 Contents 13 4 3 Unpacking 13 4 4 Prep...

Страница 3: ...tomatically Dear Customer Your Vok ra Mynute i boiler has been designed to meet and exceed the very latest standards in gas central heating technology and if cared for will give years of reliable use...

Страница 4: ...unter clockwise to reduce the tem perature range 40 C 80 C for standard central heating The automatic temperature control function SARA is set within the blank bullet points MODE SELECTOR SWITCH HEATI...

Страница 5: ...ance status table for fault indicator and boiler status 2 3 LIGHTING THE BOILER Ensure the gas and electrical supply to the boiler are turned on Turn the mode selector switch to the ON position When t...

Страница 6: ...THE SYSTEM FOR LONG PERIODS If the house is to be left unoccupied for any length of time especially during the winter the system should be thoroughly drained of all water The gas water and electricit...

Страница 7: ...rary then final Reset check appliance operation Temperature differential Final Reset check appliance operation check thermistors A08 Return thermistor fault Temporary Check return thermistor check wir...

Страница 8: ...ons These appliances are designed for use with a sealed system only consequently they are not intended for use on open vented systems This booklet is an integral part of the appliance It is therefore...

Страница 9: ...nissensedbytheelectroniccircuittoensureflamestability at the burner Once successful ignition has been achieved the electronic circuitry increases the gas rate to 75 for a period of 15minutes Thereafte...

Страница 10: ...e i30 Sides 12mm Top 150mm from casing or 25mm above flue elbow whichever is applicable Bottom 150mm Front 600mm 2 7 Connections Mynute i20 Mynute i30 Flow return 22mm Gas 15mm Safety valve 15mm Conde...

Страница 11: ...300 mm Q From the top of the vertical terminal to the roof flashing As determined by the fixed collar of the vertical terminal R To the side of a boundary 300 mm S To the side of an opening or window...

Страница 12: ...high water content it may be necessary to provide additional expansion capacity see 6 18 3 6 6 FILLING POINT A method for initial filling of the system and replacing water lost during servicing etc di...

Страница 13: ...s no requirement for a sheet of fireproof material to protect the wall 3 9 TIMBER FRAMED BUILDINGS If the appliance is to be fitted in a timber framed building it shouldbefittedinaccordancewiththeInst...

Страница 14: ...es with the local water authority regulations 3A 6 7 LOW PRESSURE SEALED SYSTEM An alternative method of filling the system would be from an independent make up vessel or tank mounted in a position at...

Страница 15: ...on its vertical axis In addition the flue may be extended from the outlet elbow in the horizontal plane see2 9 Areductionmustalsobemadetothemaximumlength see table below when additional bends are use...

Страница 16: ...d be drilled LEVEL to ensure any condense fluid that forms is allowed to drain back to the appliance The fixing holes for the wall mounting bracket should now be drilled and plugged an appropriate typ...

Страница 17: ...ect the required number of flue extensions or bends up to the maximum equivalent flue length between the boiler and vertical flue assembly Ensure that any horizontal sections of the flue system have a...

Страница 18: ...flue kit for termination The horizontal terminal is supplied with a built in converter box and cannot be shortened A 130mm hole is required for the passage of the concentric terminal through the wall...

Страница 19: ...reen yellow to EARTH connection Insertthesupplied3 AMPfuseintothefusedisolatororfusedplug Should the fly lead be unsuitable refer to 4 7 3 for details on how to connect the electrical supply directly...

Страница 20: ...UK to ensure that correct combustion is occurring see flow chart on page 36 Additionally if the gas valve has been adjusted replaced or the appliance has been converted for use with another gas type...

Страница 21: ...SERVICING Check the operation of the appliance and ensure it functions as described in section 7 Compare the performance of the appliance with its design specification The cause of any noticeable dete...

Страница 22: ...and remove the air chamber front cover Remove the AAV locking pin M from the deaerator assembly and remove the AAV assembly N Replace in the reverse order 6 8 WATER PRESSURE SWITCH fig 29 Carry out co...

Страница 23: ...electrode leads and ancillary wiring from their respective connectors Remove the retaining screws W for electrode and remove 6 12 GAS VALVE fig 31 Carry out component removal procedure as described in...

Страница 24: ...cal an external expansion vessel may be fitted to the return pipe as close to the appliance as possible 6 18 1 EXPANSION VESSELREMOVAL with sufficient clearance above fig 37 Carry out component remova...

Страница 25: ...Locate and remove the screw A2 that secures the flue gas analysis test point cover B2 Remove the clip and the fumes thermostat C2 Locate and remove the screws D2 that se cure the flue collector to th...

Страница 26: ...sition and any additional controls time clock programmer room thermostat etc calling for heat the appliance will operate in the heating mode The pump and fan will be activated via the flow temperature...

Страница 27: ...PLETION On completion of the combustion analysis check and or any gas valve adjustment refit the plug fig 40 L2 and move the mode selector through position Remove the test probe from the test point an...

Страница 28: ...at the fuse has failed but no fault is in dicated a detailed continuity check will be required to trace the fault A visual inspection of components may also assist in locating the fault 7 7 3 POLARITY...

Страница 29: ...pm GAS VALVE CALIBRATION Connect the boiler to the power supply Open the gas tap Set the function selector to OFF RESET monitor off Remove the screws E remove the casing remove the re taining screw be...

Страница 30: ...0 15 20 25 30 ROOM TEMPERATURE CURVE OFFSET DELIVERY TEMPERATURE C EXTERNAL TEMPERATURE C Fig 42 The boiler is supplied with the adjustments shown in the table Depending on plant engineering requireme...

Страница 31: ...FLOW OUTLET TEMPERATURE C T80 Maximum set point for standard T range JP7 removed T45 Maximum set point for low T range JP7 inserted Fig 43 CN8 CN7 CN6 CN5 CN12 1 JP1 JP2 JP3 JP4 JP5 JP6 JP7 JP8 CN15...

Страница 32: ...appliance can be used with the following controls twin channel programmers The appliance can be used in conjunction with typical S Plan systems and Y Plan systems Please contact Vokera technical shou...

Страница 33: ...CN2 NO NC C black black BE11 FUNCTIONAL DIAGRAM Fig 45 S W CO2 function button F S 1 Flame sensor F1 Fuse 3 15A T F External fuse 3 15A F M3 Terminal strip for electrical connection hight power P Pum...

Страница 34: ...10 0 CO2 minimum output 10 0 10 0 CO maximum output ppm 190 160 CO minimum output ppm 20 15 CO2 FUNCTIONS ACTION ON THE BUTTON DISPLAY combustion analysis mode press once burner running at maximum hea...

Страница 35: ...H FRPPLVVLRQLQJ FKHFNOLVW completed in full 7R LQVWLJDWH WKH ERLOHU JXDUDQWHH WKH ERLOHU QHHGV WR EH UHJLVWHUHG ZLWK WKH PDQXIDFWXUHU ZLWKLQ RQH PRQWK RI WKH LQVWDOODWLRQ 7R PDLQWDLQ WKH ERLOHU JXDUDQ...

Страница 36: ...OHU LQWHUORFN 3URYLGHG ALL SYSTEMS 7KH V VWHP KDV EHHQ XVKHG DQG FOHDQHG LQ DFFRUGDQFH ZLWK 6 DQG ERLOHU PDQXIDFWXUHU V LQVWUXFWLRQV Yes KDW V VWHP FOHDQHU ZDV XVHG KDW LQKLELWRU ZDV XVHG 4XDQWLW OLWU...

Страница 37: ...HSKRQH 1R DV VDIH UHJLVWHU 1R 5HFRUG W PD UDWH 2 SSP AND 2 W PLQ UDWH KHUH 3RVVLEOH 2 SSP AND 2 RPPHQWV 6LJQDWXUH SERVICE 04 DWH QJLQHHU QDPH RPSDQ QDPH 7HOHSKRQH 1R DV VDIH UHJLVWHU 1R 5HFRUG W PD UD...

Страница 38: ...R TO MINIMUM RATE In accordance with section 7 3 set boiler to operate at minimum rate to minimum load condition Allow sufficient time for combustion to stabilise YES Is CO 350ppm and CO CO2 ratio les...

Страница 39: ...39...

Страница 40: ...ies vokera co uk www vokera co uk www vokera ie Sales General Enquires T 0844 391 0999 F 0844 391 0998 Vok ra Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limited reserve t...

Отзывы: