background image

25

7.3 CHECKING THE CO

2

 AND ADJUSTING THE 

GAS VALVE

THE GAS VALVE MUST BE SET-UP OR ADJUSTED WITH 
THE AID OF A PROPERLY CALIBRATED FLUE GAS 
ANALYSER.
Isolate the appliance from the electrical supply and remove 
the appliance casing as described in 4.7.1, to gain access to 
the printed circuit board, locate and open the closing plug on 
the dash board (L2), Restore the electrical supply to the boiler 
and switch the boiler to the OFF mode. locate and press the 
CO button (see fi g. 40 pos. SW1). Press the button the num-
ber of times according the function requirement as par 7.3.1.
Set the fl ue gas analyser to read CO2 and insert the probe 
into the fl ue analysis test point.

Fig. 40

L2

SW1

use the supplied 

screwdriver to push the 

CO botton (SW1)

7.3.2 GAS VALVE MAXIMUM SETTING

Set the CO

2

 button at maximum heating (see 7.3.1), once the 

maximum heating is obtained (only yellow led blinking) check 
that it corresponds with the appropriate CO

2

 value (Maximum) 

for the respective appliance (see 2.11). If the CO

2

 reading is 

correct, proceed to gas valve minimum setting (7.3.3).
However, if the CO

2

 reading is incorrect, the maximum gas 

pressure must be adjusted as follows:



using a 2.5mm Allen key, very slowly turn the maximum ad-
justment screw (see fi g. 41) – clockwise to decrease, counter 
clockwise to increase – until the correct value is displayed on 
the CO

2

 analyser (allow time for the analyser to stabilise).

7.3.3 GAS VALVE MINIMUM SETTING

Set the CO2 button at minimum (see 7.3.1), once the minimum 
is obtained (yellow led bl green led fi xed) check that it 
corresponds with the appropriate CO2 value (Minimum) for the 
respective appliance (see 2.11). If the CO2 reading is correct, 
proceed to completion (7.3.4).
However, if the CO2 reading is incorrect, the minimum gas 
pressure must be adjusted as follows:
• locate the minimum adjustment screw (fi g. 41), using a suit-

able screwdriver remove the protection plug

• using a 4mm Allen key, very slowly turn the minimum adjust-

ment screw (see fi g. 41) - clockwise to increase, counter 
clockwise to decrease - until the correct value is displayed 
on the CO2 analyser (allow time for the analyser to stabilise).

7.3.4 COMPLETION

On completion of the combustion analysis check and/or any 
gas valve adjustment, refi t the plug (fi g. 40 

L2

) and move the 

mode selector through 

 position. Remove the test probe 

from the test point and refi t the sealing screw/s and/or cap.

IMPORTANT

A GAS TIGHTNESS CHECK MUST BE CARRIED OUT IF 

ANY GAS CARRYING COMPONENTS HAVE BEEN REMO-

VED, REPLACED OR DISTURBED.

7.4 COMBUSTION ANALYSIS TEST

A combustion analysis check can easily be carried out on the 
appliance via the test points located on the top of the appli-
ance (see 7.3).



Insert the fl ue gas analyser probe into the fl ue gas test point

7.3.1 CO

2

 FUNCTION SETTINGS

Locate the CO

 

button (see 7.3)

Select the main selector switch in position 

CO

2

 FUNCTIONS 

ACTION ON THE BUTTON 

LED STATUS

combustion analysis mode 

press once = burner running at maximum heating 

ACO

 

 

gas valve maximun setting (*) 

press twice = burner running at maximum absolute  

ACO

 

 

gas valve minimum setting 

press three time = burner running at minimum 

ACO

 

 

 

(*) this step has not to be used for the system boiler. If you fi nd in this situation press the button once again. 

NOTE

1 - Any additional pressing of CO

 

button after the third time the burner switched between maximum absolute and minimum.

2 - To restart the CO

 

function it is necessary to pass throught the 

 position with the main selector switch



Operate the boiler in combustion analysis mode (see 7.3.1) 
and compare the values with those shown in section 2 (Nat. 
Gas) or section 10 (LPG). If different adjust the gas valve 
according to 7.3.1, 7.3.2, & 7.3.3.

Note:

 If a measured CO/CO2 ratio of 0.004/1 or less AND a 

CO reading of less than 350ppm cannot be achieved, please 
contact Vokera technical for advice.

7.5 CHECKING THE EXPANSION VESSEL

Carry out the component removal procedure as described in 
6.4. You must ensure that the boiler is completely drained of 
water. Using a suitable pressure gauge, remove dust cap on 
expansion vessel and check the charge pressure.  The cor-
rect charge pressure should be 1.0 bar ± 0.1 bar. If the charge 
pressure is less, use a suitable pump to increase the charge.

NOTE

You must ensure the drain valve is in the open position whilst 
re-charging takes place. Replace the dust cap and carry out 
the relevant commissioning procedure (section 5).

fi g. 41

Minimum 

screw

Inlet gas pressure

connection

Compensation pipe 

connection

Maximum 

screw

Содержание Mynute i20

Страница 1: ...is a licensed member of the Benchmark scheme which aims to improve the standards of installation and which aims to improve the standards of installation and commissioning of domestic hot water system...

Страница 2: ...Mounting on a combustible surface 12 3A 9 Timber framed buildings 12 3A 10 Inhibitors 12 3A 11 Declaration of conformity 12 Installation Page 4 1 Delivery 13 4 2 Contents 13 4 3 Unpacking 13 4 4 Prep...

Страница 3: ...tomatically Dear Customer Your Vok ra Mynute i boiler has been designed to meet and exceed the very latest standards in gas central heating technology and if cared for will give years of reliable use...

Страница 4: ...unter clockwise to reduce the tem perature range 40 C 80 C for standard central heating The automatic temperature control function SARA is set within the blank bullet points MODE SELECTOR SWITCH HEATI...

Страница 5: ...ance status table for fault indicator and boiler status 2 3 LIGHTING THE BOILER Ensure the gas and electrical supply to the boiler are turned on Turn the mode selector switch to the ON position When t...

Страница 6: ...THE SYSTEM FOR LONG PERIODS If the house is to be left unoccupied for any length of time especially during the winter the system should be thoroughly drained of all water The gas water and electricit...

Страница 7: ...rary then final Reset check appliance operation Temperature differential Final Reset check appliance operation check thermistors A08 Return thermistor fault Temporary Check return thermistor check wir...

Страница 8: ...ons These appliances are designed for use with a sealed system only consequently they are not intended for use on open vented systems This booklet is an integral part of the appliance It is therefore...

Страница 9: ...nissensedbytheelectroniccircuittoensureflamestability at the burner Once successful ignition has been achieved the electronic circuitry increases the gas rate to 75 for a period of 15minutes Thereafte...

Страница 10: ...e i30 Sides 12mm Top 150mm from casing or 25mm above flue elbow whichever is applicable Bottom 150mm Front 600mm 2 7 Connections Mynute i20 Mynute i30 Flow return 22mm Gas 15mm Safety valve 15mm Conde...

Страница 11: ...300 mm Q From the top of the vertical terminal to the roof flashing As determined by the fixed collar of the vertical terminal R To the side of a boundary 300 mm S To the side of an opening or window...

Страница 12: ...high water content it may be necessary to provide additional expansion capacity see 6 18 3 6 6 FILLING POINT A method for initial filling of the system and replacing water lost during servicing etc di...

Страница 13: ...s no requirement for a sheet of fireproof material to protect the wall 3 9 TIMBER FRAMED BUILDINGS If the appliance is to be fitted in a timber framed building it shouldbefittedinaccordancewiththeInst...

Страница 14: ...es with the local water authority regulations 3A 6 7 LOW PRESSURE SEALED SYSTEM An alternative method of filling the system would be from an independent make up vessel or tank mounted in a position at...

Страница 15: ...on its vertical axis In addition the flue may be extended from the outlet elbow in the horizontal plane see2 9 Areductionmustalsobemadetothemaximumlength see table below when additional bends are use...

Страница 16: ...d be drilled LEVEL to ensure any condense fluid that forms is allowed to drain back to the appliance The fixing holes for the wall mounting bracket should now be drilled and plugged an appropriate typ...

Страница 17: ...ect the required number of flue extensions or bends up to the maximum equivalent flue length between the boiler and vertical flue assembly Ensure that any horizontal sections of the flue system have a...

Страница 18: ...flue kit for termination The horizontal terminal is supplied with a built in converter box and cannot be shortened A 130mm hole is required for the passage of the concentric terminal through the wall...

Страница 19: ...reen yellow to EARTH connection Insertthesupplied3 AMPfuseintothefusedisolatororfusedplug Should the fly lead be unsuitable refer to 4 7 3 for details on how to connect the electrical supply directly...

Страница 20: ...UK to ensure that correct combustion is occurring see flow chart on page 36 Additionally if the gas valve has been adjusted replaced or the appliance has been converted for use with another gas type...

Страница 21: ...SERVICING Check the operation of the appliance and ensure it functions as described in section 7 Compare the performance of the appliance with its design specification The cause of any noticeable dete...

Страница 22: ...and remove the air chamber front cover Remove the AAV locking pin M from the deaerator assembly and remove the AAV assembly N Replace in the reverse order 6 8 WATER PRESSURE SWITCH fig 29 Carry out co...

Страница 23: ...electrode leads and ancillary wiring from their respective connectors Remove the retaining screws W for electrode and remove 6 12 GAS VALVE fig 31 Carry out component removal procedure as described in...

Страница 24: ...cal an external expansion vessel may be fitted to the return pipe as close to the appliance as possible 6 18 1 EXPANSION VESSELREMOVAL with sufficient clearance above fig 37 Carry out component remova...

Страница 25: ...Locate and remove the screw A2 that secures the flue gas analysis test point cover B2 Remove the clip and the fumes thermostat C2 Locate and remove the screws D2 that se cure the flue collector to th...

Страница 26: ...sition and any additional controls time clock programmer room thermostat etc calling for heat the appliance will operate in the heating mode The pump and fan will be activated via the flow temperature...

Страница 27: ...PLETION On completion of the combustion analysis check and or any gas valve adjustment refit the plug fig 40 L2 and move the mode selector through position Remove the test probe from the test point an...

Страница 28: ...at the fuse has failed but no fault is in dicated a detailed continuity check will be required to trace the fault A visual inspection of components may also assist in locating the fault 7 7 3 POLARITY...

Страница 29: ...pm GAS VALVE CALIBRATION Connect the boiler to the power supply Open the gas tap Set the function selector to OFF RESET monitor off Remove the screws E remove the casing remove the re taining screw be...

Страница 30: ...0 15 20 25 30 ROOM TEMPERATURE CURVE OFFSET DELIVERY TEMPERATURE C EXTERNAL TEMPERATURE C Fig 42 The boiler is supplied with the adjustments shown in the table Depending on plant engineering requireme...

Страница 31: ...FLOW OUTLET TEMPERATURE C T80 Maximum set point for standard T range JP7 removed T45 Maximum set point for low T range JP7 inserted Fig 43 CN8 CN7 CN6 CN5 CN12 1 JP1 JP2 JP3 JP4 JP5 JP6 JP7 JP8 CN15...

Страница 32: ...appliance can be used with the following controls twin channel programmers The appliance can be used in conjunction with typical S Plan systems and Y Plan systems Please contact Vokera technical shou...

Страница 33: ...CN2 NO NC C black black BE11 FUNCTIONAL DIAGRAM Fig 45 S W CO2 function button F S 1 Flame sensor F1 Fuse 3 15A T F External fuse 3 15A F M3 Terminal strip for electrical connection hight power P Pum...

Страница 34: ...10 0 CO2 minimum output 10 0 10 0 CO maximum output ppm 190 160 CO minimum output ppm 20 15 CO2 FUNCTIONS ACTION ON THE BUTTON DISPLAY combustion analysis mode press once burner running at maximum hea...

Страница 35: ...H FRPPLVVLRQLQJ FKHFNOLVW completed in full 7R LQVWLJDWH WKH ERLOHU JXDUDQWHH WKH ERLOHU QHHGV WR EH UHJLVWHUHG ZLWK WKH PDQXIDFWXUHU ZLWKLQ RQH PRQWK RI WKH LQVWDOODWLRQ 7R PDLQWDLQ WKH ERLOHU JXDUDQ...

Страница 36: ...OHU LQWHUORFN 3URYLGHG ALL SYSTEMS 7KH V VWHP KDV EHHQ XVKHG DQG FOHDQHG LQ DFFRUGDQFH ZLWK 6 DQG ERLOHU PDQXIDFWXUHU V LQVWUXFWLRQV Yes KDW V VWHP FOHDQHU ZDV XVHG KDW LQKLELWRU ZDV XVHG 4XDQWLW OLWU...

Страница 37: ...HSKRQH 1R DV VDIH UHJLVWHU 1R 5HFRUG W PD UDWH 2 SSP AND 2 W PLQ UDWH KHUH 3RVVLEOH 2 SSP AND 2 RPPHQWV 6LJQDWXUH SERVICE 04 DWH QJLQHHU QDPH RPSDQ QDPH 7HOHSKRQH 1R DV VDIH UHJLVWHU 1R 5HFRUG W PD UD...

Страница 38: ...R TO MINIMUM RATE In accordance with section 7 3 set boiler to operate at minimum rate to minimum load condition Allow sufficient time for combustion to stabilise YES Is CO 350ppm and CO CO2 ratio les...

Страница 39: ...39...

Страница 40: ...ies vokera co uk www vokera co uk www vokera ie Sales General Enquires T 0844 391 0999 F 0844 391 0998 Vok ra Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limited reserve t...

Отзывы: