33
MAXIN 24e & 28e
Constant monitoring of the temperature of
the primary water by the thermistor will
regulate the gas rate between high & low to
maintain an average heat input.
When the appliance has reached the set
temperature and the burner is off, the pump
will continue to run to circulate the primary
water around the c/h system.
If supply to the appliance is broken e.g. by
a room thermostat or timeclock the burner
is extinguished and the pump stops, but the
fan will continue to run until the primary
water temperature is below 80°C.
Should there be a restriction in the heating
circuit reducing the flow rate to below 350 l/
hour (1.28 gpm) the flow switch will deacti-
vate and de-energise the gas valve.
FAULT FINDING GUIDES
On the following pages are the fault finding guides, be sure to read the notes below before
begining any fault finding
NOTES:
1.
To ensure correct fault diagnosis it is important that these guides are carried out in the set order.
2.
Check the electrical supply polarity is correct before carrying out fault finding (lockout will occur if the
polarity is reversed).
3.
To ensure that internal/external controls (if fitted) do not interfere with fault finding, disconnect the
wires from terminals 1 & 2 and 4 & 5 (labelling them in the process to ensure correct reconnection) and
provide a solid link between 1 & 2 and 4 & 5.