Manual VIPA System 200V
Chapter 4 CP 240 - serial
HB97E - CP - Rev. 11/30
4-25
The delayed acknowledgment time defines the maximum time for the
acknowledgment from the partner when the connection is being
established. The QVZ is specified in units of 20ms.
Range: 0 ... 255
Default: 25
BWZ is the max. time between acknowledgement of a request telegram
(DLE) and STX of the answer telegram.
The BWZ is specified in units of 20ms.
Range: 0 ... 255
Default: 100
Maximum number of allowed attempts for a CP 240 to establish a
connection.
Range: 0 ... 255
Default: 3
With exceeding the block waiting time (BWZ) you can set the maximum
number of repetitions for the request telegram by means of the parameter
DBL. If these attempts are unsuccessful, the transmission is interrupted.
Range: 0 ... 255
Default: 6
A communication partner has a high priority when its transmit request
supersedes the transmit request of a partner. When the priority is lower, it
must take second place after the transmit request of the partner.
The priorities of the two partners must be different for the 3964(R) and
RK512 protocols.
You may select one of the following settings:
0:
low
1:
high
Default: 0 (low)
Delayed
acknowledgment
time (QVZ)
(for 3964(R), RK512)
Block delay time
(BWZ)
(for 3964(R), RK512)
STX repetitions
(for 3964(R), RK512)
Repetitions of
data blocks (DBL)
if exceeding BWZ
(for 3964(R), RK512)
Priority
(for 3964(R), RK512)
Содержание CP 240 RS232
Страница 1: ...Manual VIPA System 200V CP Order No VIPA HB97E_CP Rev 11 30...
Страница 2: ...L...
Страница 14: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E CP Rev 11 30...
Страница 126: ...Chapter 5 CP 240 EnOcean Manual VIPA System 200V 5 32 HB97E CP Rev 11 30...
Страница 144: ...Chapter 6 CP 240 M Bus Manual VIPA System 200V 6 18 HB97E CP Rev 11 30...
Страница 148: ...Index Manual VIPA System 200V A 4 HB97E CP Rev 11 30 M Stich...