Chapter 4 CP 240 - serial
Manual VIPA System 200V
4-30
HB97E - CP - Rev. 11/30
Number of
data bits
that represent a character.
The parity is depending on the value even or odd. For the purposes of the
parity check, the information bits are expanded by the parity bit. The value
of the parity bit ("0" or "1") completes the value of all the bits to obtain a
pre-arranged state. If the parity was not specified, the parity bit is set to "1"
but it is not included in the assessment.
The stop bits are appended to each character and signify the end of the
character.
Default: 13h (Data bits: 8, Parity: none, Stop bit: 1)
Set here in slave mode the Modbus slave address.
Range: 1 ... 255
Default: 1
This mode is for internal tests. This function should always be de-activated.
Range: 0, 1
Default: 0
In master mode here has to be set a delay time in ms. With "0" the delay
time is evaluated automatically depending on the protocol with the following
formula:
Modbus ASCII:
s
Baudrate
ms
ms
⋅
+
2926000
50
with baud rate in Bit/s
Modbus RTU:
s
Baudrate
ms
ms
⋅
+
5190000
50
with baud rate in Bit/s
In slave mode this parameter is ignored.
Data bits
Parity
Stop bits
Address
Debug
Delay time
Содержание CP 240 RS232
Страница 1: ...Manual VIPA System 200V CP Order No VIPA HB97E_CP Rev 11 30...
Страница 2: ...L...
Страница 14: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E CP Rev 11 30...
Страница 126: ...Chapter 5 CP 240 EnOcean Manual VIPA System 200V 5 32 HB97E CP Rev 11 30...
Страница 144: ...Chapter 6 CP 240 M Bus Manual VIPA System 200V 6 18 HB97E CP Rev 11 30...
Страница 148: ...Index Manual VIPA System 200V A 4 HB97E CP Rev 11 30 M Stich...