Chapter 2 Assembly and installation guidelines
Manual VIPA System 200V
2-8
HB97E - CP - Rev. 11/30
Wiring
Most peripheral modules are equipped with a 10pole or an 18pole
connector. This connector provides the electrical interface for the signaling
and supply lines of the modules.
The modules carry spring-clip connectors for the interconnections and
wiring.
The spring-clip connector technology simplifies the wiring requirements for
signaling and power cables.
In contrast to screw terminal connections, spring-clip wiring is vibration
proof. The assignment of the terminals is contained in the description of the
respective modules.
You may connect conductors with a wire cross-section from 0.08mm
2
up to
2.5mm
2
(max. 1.5mm
2
for 18pole connectors).
The following figure shows a module with a 10pole connector.
Note!
The spring-clip is destroyed if you insert the screwdriver into the opening
for the hook-up wire!
Make sure that you only insert the screwdriver into the square hole of the
connector!
Outline
Round aperture
for wires
Rectangular opening
for screwdriver
Pin no.
Pin no.