Chapter 5 CP 240 - EnOcean
Manual VIPA System 200V
5-30
HB97E - CP - Rev. 11/30
In case of replacement send a SET_IDBASE telegram with the following
structure from your CPU to the module (transceiver). Use the address of
the module you want to replace as new ID base:
0xAB
ID for transmission telegram
0x18
ORG ID for SET_IDBASE
IDBaseByte3
Byte 3 new ID base
IDBaseByte2
Byte 2 new ID base
IDBaseByte1
Byte 1 new ID base
IDBaseByte0
Byte 0 new ID base (Bit 6...0 irrelevant)
X
irrelevant
...
...
X
irrelevant
0x8B
0x58
←
←
←
←
OK
–
ID base was set
To take over the ID base during runtime you have to execute a reset via
FC 9. Otherwise the new ID base is available after a reboot of the CPU.
In case of an error you receive one of the following messages. Here the old
ID base remains valid.
0x8B
0x19
←
←
←
←
ERR
More than 10 ID base changes are not permitted
0x8B
0x1A
←
←
←
←
ERR_IDRANGE
ID base is outside the valid range
(0xFF800000 ... 0xFFFFFFFF).
Control your ID settings and send the telegram once more.
SET_IDBASE
Possible respond
telegram