Manual VIPA System 200V
Chapter 5 CP 240 - EnOcean
HB97E - CP - Rev. 11/30
5-29
Exchange module and set ID base
Since the ID base of every module is different, you have in case of
replacement the option to change the ID base of a module for up to 10
times by means of a SET_IDBASE telegram. Consequently the newly
adjustment of the actuators to the replacement module is no longer
necessary. After successful transfer of the ID base you have either to
reboot your CPU or reset it via FC 9.
Please regard that only the upper 25 bits are taken over as ID base. The
remaining 7 bits you may specify via your user application during runtime
and herewith address multiple actuators.
With RD_IDBASE the current ID base of your module may be requested.
0xAB
ID for transmission telegram
0x58
ORG ID for RD_IDBASE
X
Irrelevant
...
...
X
Irrelevant
RD_IDBASE reports back the current ID base of the module in form on an
INF_IDBASE telegram. The telegram has the following structure:
0x8B
ID for reception telegram
0x98
ORG-ID for INF_IDBASE
IDBaseByte3
Byte 3 current ID base
IDBaseByte2
Byte 2 current ID base
IDBaseByte1
Byte 1 current ID base
IDBaseByte0
Byte 0 current ID base (Bit 6...0 irrelevant)
X
irrelevant
...
...
X
irrelevant
Overview
ID base request
RD_IDBASE
INF_IDBASE
Содержание CP 240 RS232
Страница 1: ...Manual VIPA System 200V CP Order No VIPA HB97E_CP Rev 11 30...
Страница 2: ...L...
Страница 14: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E CP Rev 11 30...
Страница 126: ...Chapter 5 CP 240 EnOcean Manual VIPA System 200V 5 32 HB97E CP Rev 11 30...
Страница 144: ...Chapter 6 CP 240 M Bus Manual VIPA System 200V 6 18 HB97E CP Rev 11 30...
Страница 148: ...Index Manual VIPA System 200V A 4 HB97E CP Rev 11 30 M Stich...