The diagnosis is independent from the operating mode of the CPU.
You may store a max. of 100 diagnostic entries in the CPU. The fol-
lowing page shows an overview of the VIPA specific Event-IDs.
Overview of the Event-IDs
Event-ID
Description
0x115C
Vendor-specific interrupt (OB 57) at EtherCAT
OB: OB number (57)
ZInfo1: Logical address of the slave, which has released the interrupt
ZInfo2: Interrupt type
ZInfo3: Reserved
0xE003
Error on accessing the periphery
ZInfo1: Periphery address
ZInfo2: Slot
0xE004
Multiple parametrization of a periphery address
ZInfo1: Periphery address
ZInfo2: Slot
0xE005
Internal error - Please contact the VIPA Hotline!
0xE006
Internal error - Please contact the VIPA Hotline!
0xE007
Configured in-/output bytes do not fit into periphery area
0xE008
Internal error - Please contact the VIPA Hotline!
0xE009
Error on accessing the standard backplane bus
0xE010
There is a undefined module at the backplane bus
ZInfo2: Slot
ZInfo3: Type ID
0xE011
Master project engineering at slave CPU not possible or wrong slave
configuration
0xE012
Error at parametrization
0xE013
Error at shift register access to standard bus digital modules
0xE014
Error at Check_Sys
0xE015
Error at access to the master
ZInfo2: Slot of the master (32=page frame master)
0xE016
Maximum block size at master transfer exceeded
ZInfo1: Periphery address
ZInfo2: Slot
0xE017
Error at access to integrated slave
0xE018
Error at mapping of the master periphery
0xE019
Error at standard back plane bus system recognition
0xE01A
Error at recognition of the operating mode (8 / 9 bit)
VIPA System 300S CPU
Deployment CPU 315-2AG13
VIPA specific diagnostic entries
HB140 | CPU | 315-2AG13 | GB | Rev. 14-40
72