RN
(RUN)
ER
(ERR)
DE
IF
Meaning
●
○
○
○
Master has bus parameters and is in RUN without
slaves.
●
○
BB
○
Master is in "clear" state (safety state). The inputs of
the slaves may be read. The outputs are disabled.
●
○
●
○
Master is in "operate" state, this means data exchange
between master and slaves. The outputs may be
accessed.
●
●
●
○
CPU is in RUN, at least 1 slave is missing.
●
●
BB
○
CPU is in STOP, at least 1 slave is missing.
○
○
○
●
Initialization error at faulty parametrization.
○
●
○
●
Waiting state for start command from CPU.
on: ● | off: ○ | blinking (2Hz): BB
Slave operation
RN
(RUN)
ER
(ERR)
DE
IF
Meaning
green
red
green
red
○
○
○
○
Slave has no project respectively PtP is active.
BB
○
○
○
Slave is without master.
BB*
○
BB*
○
* Alternate flashing at configuration faults.
●
○
●
○
Slave exchanges data between master.
on: ● | off: ○ | blinking (2Hz): BB
4.3 Technical data
Order no.
315-2AG13
Type
CPU 315SB/DPM
SPEED-Bus
-
Technical data power supply
Power supply (rated value)
DC 24 V
Power supply (permitted range)
DC 20.4...28.8 V
Reverse polarity protection
ü
Current consumption (no-load operation)
200 mA
Current consumption (rated value)
1 A
Inrush current
5 A
VIPA System 300S CPU
Hardware description
Technical data
HB140 | CPU | 315-2AG13 | GB | Rev. 14-40
31