The PROFIBUS line has to be terminated with its ripple
resistor. Please make sure to terminate the last partici-
pants on the bus at both ends by activating the terminating
resistor.
In PROFIBUS all participants are wired parallel. For that purpose, the
bus cable must be feed-through. Via the order number 972-0DP10
you may order the bus connector "EasyConn". This is a bus con-
nector with switchable terminating resistor and integrated bus diag-
nostic.
Dimensions in mm
0°
45°
90°
A
64
61
66
B
34
53
40
C
15.8
15.8
15.8
EasyConn bus con-
nector
VIPA System 300S CPU
Deployment PROFIBUS communication
PROFIBUS installation guidelines