Chapter 4 Deployment CPU 313SC/DPM
Manual VIPA System 300S SPEED7
4-34
HB140E - CPU SC - RE_313-6CF03 - Rev. 07/45
1. Get the RUN-STOP lever of your CPU in position STOP. Turn off the
voltage supply. Plug the MMC with the firmware files into the CPU.
Please take care of the correct plug-in direction of the MMC. Turn on
the voltage supply.
2. After a short boot-up time, the alternate blinking of the LEDs SF and
FRCE shows that at least a more current firmware file was found on
the MMC.
3. You start the transfer of the firmware as soon as you tip the
RUN/STOP lever downwards to MRES within 10s.
4. During the update process, the LEDs SF and FRCE are alternately
blinking and MMC LED is on. This may last several minutes.
5. The update is successful finished when the LEDs PWR, STOP, SF,
FRCE and MCC are on. If they are blinking fast, an error occurred.
6. Turn Power OFF and ON. Now it is checked by the CPU, whether
further current firmware versions are available at the MMC. If so, again
the LEDs SF and FRCE flash after a short start-up period. Continue
with point 3.
If the LEDs do not flash, the firmware update is ready.
Now a
factory reset
should be executed (see next page). After that the
CPU is ready for duty.
Power OFF/ON
RUN
STOP
MRES
RUN
STOP
MRES
PWR
RUN
STOP
SF
FRCE
MCC
PLC
RUN
STOP
MRES
Insert MMC
PWR
RUN
STOP
SF
FRCE
MCC
PLC
10 Sec.
Tip
PWR
RUN
STOP
SF
FRCE
MCC
PLC
PWR
RUN
STOP
SF
FRCE
MCC
PLC
Preparation
Firmware
recognized
at MMC
Start update
Update runs
PWR
RUN
STOP
SF
FRCE
MCC
PLC
Update
terminates
error free
PWR
RUN
STOP
SF
FRCE
MCC
PLC
Error
1
2
3
4
Power
OFF/ON
5
6
Transfer firmware
from MMC into
CPU
Содержание 313-6CF03
Страница 2: ...Lerrzeichen ...
Страница 40: ...Chapter 3 Hardware description Manual VIPA System 300S SPEED7 3 14 HB140E CPU SC RE_313 6CF03 Rev 07 45 ...
Страница 122: ...Chapter 5 Deployment I O periphery Manual VIPA System 300S SPEED7 5 36 HB140E CPU SC RE_313 6CF03 Rev 07 45 ...
Страница 140: ...Chapter 6 Deployment PtP communication Manual VIPA System 300S SPEED7 6 18 HB140E CPU SC RE_313 6CF03 Rev 07 45 ...