Chapter 6 Deployment PtP communication
Manual VIPA System 300S SPEED7
6-8
HB140E - CPU SC - RE_313-6CF03 - Rev. 07/45
Deployment RS485 interface
The RS485 interface X3 of the CPU 313SC/DPM may be set to PtP
communication (
p
oint-
t
o-
p
oint) by means of a hardware configuration.
Parameterization and communication happens by means of SFCs. The
following characteristics distinguish the RS485 interface:
•
Logical states represented by voltage differences between the two cores
of a twisted pair cable
•
Serial bus connection in two-wire technology using half duplex mode
•
Data communications up to a max. distance of 500m
•
Data communication rate up to 115.2kBaud
9pin SubD jack
Pin
RS485
1 n.c.
2 M24V
3
RxD/TxD-P (Line B)
4 RTS
5 M5V
6 P5V
7 P24V
8
RxD/TxD-N (Line A)
5
4
3
2
1
9
8
7
6
9 n.c.
RxD/TxD-P (B)
RxD/TxD-N (A)
shield
CPU - RS485