Manual VIPA System 300S SPEED7
Chapter 6 Deployment PtP communication
HB140E - CPU SC - RE_313-6CF03 - Rev. 07/45
6-13
Return values of the block:
Error code Description
0000h
Send data - ready
1000h
Nothing sent (data length 0)
20xxh
Protocol executed error free with xx bit pattern for
diagnosis
7001h
Data is stored in internal buffer - active (busy)
7002h
Transfer - active
80xxh
Protocol executed with errors with xx bit pattern for
diagnosis (no acknowledgement by partner)
90xxh
Protocol not executed with xx bit pattern for diagnosis (no
acknowledgement by partner)
8x24h
Error in SFC parameter x, where x:
1: Error in "DataPtr"
2: Error in "DataLen"
8122h
Error in parameter "DataPtr" (e.g. DB too short)
807Fh Internal
error
809Ah
Interface not found or interface is used for Profibus
809Bh
Interface not configured
ASCII
Value
Description
9000h
Buffer overflow (no data send)
9002h
Data too short (0Byte)
STX/ETX
Value
Description
9000h
Buffer overflow (no data send)
9001h
Data too long (>1024Byte)
9002h
Data too short (0Byte)
9004h
Character not allowed
3964R
Value
Description
2000h
Send ready without error
80FFh
NAK received - error in communication
80FEh
Data transfer without acknowledgement of partner or error
at acknowledgement
9000h
Buffer overflow (no data send)
9001h
Data too long (>1024Byte)
9002h
Data too short (0Byte)
RetVal SFC 217
(Error message
SER_SND)
Protocol specific
RetVal values