CPU 313SC/DPM
The SC-CPU bases upon the SPEED7 technology. This supports the CPU
at programming and communication by means of co-processors that
causes a power improvement for highest needs.
The CPU is programmed in STEP
7 from Siemens. For this you may use
WinPLC7 from VIPA or the Siemens SIMATIC Manager.
The CPU with integrated Ethernet-PG/OP channel, a MPI- and RS485-slot
simplifies the integration of the CPU into an existing network or the
connection of additional peripheral equipment.
The user application is stored in the battery buffered RAM or on an
additionally pluggable MMC storage module.
The CPU has an integrated work memory. During program run the total
memory is divided into 50% for program code and 50% for data.
There is the possibility to extend the total memory to its maximum by
means of a MCC memory extension card.
The CPU has an Ethernet interface for PG/OP communication. After the
assignment of IP address parameters by "Assign Ethernet Address"
respectively by a "minimum project" the Ethernet PG/OP channel may
directly be addressed by means of the "PLC" functions to program and
remote control the CPU. A max. of 2 PG/OP connections is available.
You may also access the CPU with a visualization software via these
connections.
The CPU has an integrated Profibus DP master. Via the DP master with a
data range of 1kByte for in- and output up to 125 DP slaves may be
addressed. The project engineering takes place in WinPLC7 from VIPA or
in the hardware configurator from Siemens. Please regard there may be a
delimitation of the maximum number of configurable DP slaves by the use
of the Siemens SIMATIC manager.
The Profibus part may also be used as "intelligent" DP slave. More may be
found at "Deployment Profibus communication".
•
Wiring by CageClamps at the front connector
•
Core cross-section 0.08...2.5mm
2
•
Total isolation of the wiring at module change
•
Potential separation of all modules to the backplane bus
•
ESD/Burst acc. IEC 61000-4-2/IEC 61000-4-4 (up to level 3)
•
Shock resistance acc. IEC 60068-2-6 / IEC 60068-2-27 (1G/12G)
Overview
Memory
management
Integrated
Ethernet-PG/OP-
channel
Integrated
Profibus DP
master
Operation Security