A
System specific event IDs
Chapter 4.19 ‘Diagnostic entries’ on page 94
Event ID
Description
0x115C
Vendor-specific interrupt (OB 57) at EtherCAT
OB : OB number
ZINFO1 : Logical address of the slave that triggered the interrupt
ZINFO2 : Interrupt type
0: Reserved
1: Diagnostic interrupt (incoming)
2: Hardware interrupt
3: Pull interrupt
4: Plug interrupt
5: Status interrupt
6: Update interrupt
7: Redundancy interrupt
8: Controlled by the supervisor
9: Enabled
10: Wrong sub module plugged
11: Restoration of the sub module
12: Diagnostic interrupt (outgoing)
13: Cross traffic connection message
14: Neighbourhood change message
15: Synchronisation message (bus)
16: Synchronisation message (device)
17: Network component message
18: Clock synchronisation message (bus)
31: Pull interrupt module
32: Vendor specific interrupt min.
33: Vendor specific interrupt topology change
127: Vendor specific interrupt max.
ZINFO3 : CoE error code
0xE003
Error on accessing the periphery
ZINFO1 : Transfer type
ZINFO2 : Periphery address
ZINFO3 : Slot
0xE004
Multiple configuration of a periphery address
ZINFO1 : Periphery address
ZINFO2 : Slot
Event IDs
VIPA System SLIO
System specific event IDs
HB300 | CPU | 013-CCF0R00 | en | 17-20