3.
To get the stations and their MAC address, use the [Browse] button or type in the
MAC Address. The Mac address may be found at the 1. label beneath the front flap
of the CPU.
4.
Choose if necessary the known MAC address of the list of found stations.
5.
Either type in the IP configuration like IP address, subnet mask and gateway.
6.
Confirm with [Assign IP configuration].
ð
Direct after the assignment the Ethernet PG/OP channel may be reached online
by these address data. The value remains as long as it is reassigned, it is over-
written by a hardware configuration or an factory reset is executed.
1.
Open the Siemens hardware configurator and configure the Siemens CPU 314C-2
PN/DP (314-6EH04-0AB0 V3.3).
2.
For the Ethernet PG/OP channel you have to configure at slot 4 a Siemens CP
343-1 (SIMATIC 300 \ CP 300 \ Industrial Ethernet \CP 343-1 \ 6GK7 343-1EX30
0XE0 V3.0).
CAUTION!
Please configure the diagnostic addresses of the CP343-1EX30 for
‘PN-IO’
,
‘Port1’
and
‘Port2’
so that there is no overlap in the
peripheral input area. Otherwise, your CPU will not start and you
will get the diagnostic entry 0xE904. These address overlaps can
not be recognized by the Siemens SIMATIC Manager.
3.
Open the property window via double-click on the CP 343-1EX30 and enter for the
CP at
‘Properties’
the IP address data, which you have assigned before.
4.
Assign the CP to a
‘Subnet’
. Without assignment the IP address data are not used!
5.
Transfer your project.
4.6.1 Time-of-day synchronization
In the NTP mode (
N
etwork
T
ime
P
rotocol) the module sends as client time-of-day queries
at regular intervals to all configured NTP servers within the sub net. You can define up to
4 NTP server. Based on the response from the servers, the most reliable and most exact
time-of-day is determined. Here the time with the lowest
stratum
is used.
Stratum 0
is the
time standard (atomic clock).
Stratum 1
are directly linked to this NTP server. Using the
NTP method, clocks can be synchronized over subnet boundaries. The configuration of
the NTP servers is carried out in the Siemens SIMATIC Manager via the CP, which is
already configured.
Take IP address parame-
ters in project
NTP method
VIPA System SLIO
Deployment CPU 013-CCF0R00
Hardware configuration - Ethernet PG/OP channel > Time-of-day synchronization
HB300 | CPU | 013-CCF0R00 | en | 17-20