To attach the shield the mounting of shield bus carriers are necessary. The shield bus
carrier (available as accessory) serves to carry the shield bus to connect cable shields.
1.
Each System SLIO module has a carrier hole for the shield bus carrier. Push the
shield bus carrier, until they engage into the module. With a flat mounting rail for
adaptation to a flat mounting rail you may remove the spacer of the shield bus car-
rier.
2.
Put your shield bus into the shield bus carrier.
3.
Attach the cables with the accordingly stripped cable screen and fix it by the shield
clamp with the shield bus.
2.5.2 Wiring periphery modules
CAUTION!
Do not connect hazardous voltages!
If this is not explicitly stated in the corresponding module description,
hazardous voltages are not allowed to be connected to the corresponding
terminal module!
With wiring the terminal modules, terminals with spring clamp technology are used for
wiring. The spring clamp technology allows quick and easy connection of your signal and
supply lines. In contrast to screw terminal connections this type of connection is vibration
proof.
U
max
240V AC / 30V DC
I
max
10A
Cross section
0.08 ... 1.5mm
2
(AWG 28 ... 16)
Stripping length 10mm
1
Pin number at the connector
2
Opening for screwdriver
3
Connection hole for wire
Terminal module terminals
Data
Wiring procedure
VIPA System SLIO
Basics and mounting
Wiring > Wiring periphery modules
HB300 | CPU | 013-CCF0R00 | en | 17-20