The short description of the Siemens CPU is CPU 314C-2 PN/DP
(314-6EH04-0AB0 V3.3).
n
Order No. / Firmware
–
Order number and firmware are identical to the details in the "hardware catalog"
window.
n
Name
–
The Name field provides the short description of the CPU.
–
If you change the name the new name appears in the Siemens SIMATIC Man-
ager.
n
Plant designation
–
Here is the possibility to specify a plant designation for the CPU.
–
This plant designation identifies parts of the plant according to their function.
–
Its structure is hierarchic according to IEC 81346-1.
n
Location designation
–
The location designation is part of the resource designation.
–
Here the exact location of your module within a plant may be specified.
n
Comment
–
In this field information about the module may be entered.
n
Startup when expected/actual configuration differs
–
If the checkbox for
‘Startup when expected/actual configuration differ’
is dese-
lected and at least one module is not located at its configured slot or if another
type of module is inserted there instead, then the CPU does not switch to RUN
mode and remains in STOP mode.
–
If the checkbox for
‘Startup when expected/actual configuration differ’
is selected,
then the CPU starts even if there are modules not located in their configured slots
of if another type of module is inserted there instead, such as during an initial
system start-up.
n
Monitoring time for ready message by modules [100ms]
–
This operation specifies the maximum time for the ready message of every con-
figured module after PowerON.
–
Here connected PROFIBUS DP slaves are also considered until they are parame-
terized.
–
If the modules do not send a ready message to the CPU by the time the moni-
toring time has expired, the actual configuration becomes unequal to the preset
configuration.
n
Monitoring time for transfer of parameters to modules [100ms]
–
The maximum time for the transfer of parameters to parameterizable modules.
–
Here connected PROFINET IO devices also considered until they are parameter-
ized.
–
If not every module has been assigned parameters by the time this monitoring
time has expired; the actual configuration becomes unequal to the preset configu-
ration.
n
Update OB1 process image cyclically
–
This parameter is not relevant.
n
Scan cycle monitoring time
–
Here the scan cycle monitoring time in milliseconds may be set.
–
If the scan cycle time exceeds the scan cycle monitoring time, the CPU enters the
STOP mode.
–
Possible reasons for exceeding the time are:
- Communication processes
- a series of interrupt events
- an error in the CPU program
General
Startup
Cycle/Clock memory
VIPA System SLIO
Deployment CPU 013-CCF0R00
Setting standard CPU parameters > Parameter CPU