SERVICE POINTERS (Check General Procedure)
SYMPTOM
PROBABLE REASON
CORRECTION
Regulator does not
Diaphragm or seat dirty, damaged or frozen.
Clean or replace. Clean strainer.
shut off flow.
Diaphragm follower stuck or damaged.
Clean or replace. Install follower carefully.
Piston jammed with excess dirt.
Remove and polish piston and bore with
crocus cloth. Clean valve and strainer.
Throttling plug leaking due to excess
Clean or replace. If used on liquid, check for
dirt or damage.
erosion due to excessive flash gas. Reduce
flash gas by sub-cooling or by reducing
pressure drop across valve by providing
restriction at valve outlet.
Diaphragm and seat eroded due to flash gas.
Replace. Reduce flash gas by sub-cooling or by
reducing pressure drop across regulator by
providing restriction at valve outlet.
Regulator does not
A4A (inlet) Pressure Regulator Diaphragm
Replace. If Range D make sure has 2
open.
ruptured or badly deformed.
diaphragms.
Diaphragm follower stuck, damaged
Clean or replace. Install follower carefully.
or frozen.
Piston worn, too much clearance.
Replace piston. Check for reason. If used on
liquid, check for flash gas.
Regulator Operation
Diaphragm or seat dirty or damaged.
Clean or replace. Clean strainer.
erratic.
Diaphragm follower has dirt on the outside
Clean or replace.
diameter or outside diameter is damaged.
Other system components, line controllers,
Adjust, repair or replace.
thermostats, etc. , erratic.
Regulator too far oversized.
Check load. Replace with smaller regulator or
investigate use of Reduced Capacity Plug Kit.
Pressure drop across
Inlet or outlet restricted.
Check for restriction. Clean strainer.
regulator too high.
Regulator too small.
Replace with proper size regulator.
Large amount of flash gas in liquid line.
Reduce flash gas by sub-cooling. Reduce line
restriction by increasing line size, particularly
at the regulator outlet. Replace with larger
regulator.
High pressure drop causes high rate of
Increase pipe size at the outlet of the
expansion of gas at regulator outlet.
regulator.
Regulator does not open all the way.
Check piston for wear. Replace, if needed.
Содержание VSM 71-701
Страница 1: ...1 VPN 35391S February 2006 Rev 05 Price 60 00...
Страница 2: ...2...
Страница 20: ...20...
Страница 52: ...53 Pre Start Up Check List...
Страница 99: ...99 Recommended Spare Parts List...
Страница 104: ...104 Gate Rotor...
Страница 110: ...110 Main Rotor VSS...
Страница 112: ...112 Main Rotor VSR...
Страница 114: ...114 Slide Valve Cross Shafts and End Plate...
Страница 118: ...118 Capacity Slide Volume Slide Carriage Assembly Slide Valve Carriage Assembly...
Страница 134: ...134 Miscellaneous Frame Components VSS Screw Compressor VSR Mini Screw Compressor...
Страница 138: ...138 C FlangeAdapter Components 630 620 610 640 601 641 630 601 620 610 640 641 642 650 651...
Страница 140: ...140 Replacement Parts Tools...
Страница 144: ...144 GaterotorAssembly...
Страница 148: ...148 Main Rotor Slide Valve Cross Shafts and End Plate Models 71 401 Only Counter clockwise...
Страница 151: ...151 See Next Page for Models 501 701 Main Rotor Slide Valve Cross Shafts and End Plate V S M Parts List...
Страница 152: ...152 Main Rotor Slide Valve Cross Shafts and End Plate Model 501 701 Only Clockwise...
Страница 154: ...154 Volume Ratio Capacity Slide Carriage Assembly Slide Valve Carriage Assembly...
Страница 158: ...158 Miscellaneous Frame Components Model VSM 501 701 Model VSM 71 401...
Страница 160: ...160 Replacement Parts Accessories Housing Accessories C Flange Assembly...
Страница 166: ...166 Haight Pumps...
Страница 170: ...3 Refrigerating Specialties Division...
Страница 184: ...C A R T R I D G E H E A T E R S Hi Temp Cartridge heaters are designed for optimum performance above and beyond the norm...
Страница 236: ......
Страница 237: ......
Страница 238: ......
Страница 243: ......
Страница 244: ...168...