Fault
code
on the
display
Const.
Weath.-
comp.
System char-
acteristics
Cause
Measures
Fd
X
X
Burner
blocked
Fault at the
burner con-
trol unit
Check ignition
electrodes and
connecting
cables. Check
whether a strong
interference
(EMC) field exists
near the equip-
ment. Press
"
E
RESET" ; re-
place control unit
if the fault is not
removed.
FE
X
X
Burner
blocked or in a
fault state
Strong inter-
ference
(EMC) field
nearby or
faulty main
PCB
Start the equip-
ment again. Re-
place the control
unit if the equip-
ment will not re-
start.
FF
X
X
Burner
blocked or in a
fault state
Strong inter-
ference
(EMC) field
nearby, or in-
ternal fault
Start the equip-
ment again. Re-
place the control
unit if the equip-
ment will not re-
start.
Fault codes
(cont.)
88
Troubleshooting
5592
817
GB
Содержание VITOPEND 200
Страница 9: ...Installing the boiler and making all connections 9 Installation sequence 5592 817 GB Installation...
Страница 12: ...Opening the control unit casing 12 Installation sequence 5592 817 GB...
Страница 16: ...Fitting the programming unit into the control unit 16 Installation sequence 5592 817 GB...
Страница 17: ...Fitting the front panel 17 Installation sequence 5592 817 GB Installation...
Страница 113: ...Connection and wiring diagram internal connections 113 Designs 5592 817 GB Service...
Страница 119: ...Parts lists cont 119 Parts lists 5592 817 GB Service...
Страница 120: ...Parts lists cont 120 Parts lists 5592 817 GB...
Страница 121: ...Parts lists cont 121 Parts lists 5592 817 GB Service...
Страница 122: ...Parts lists cont 122 Parts lists 5592 817 GB...
Страница 130: ...130 5592 817 GB...
Страница 131: ...131 5592 817 GB...