Parameter address
A5:...
With heating circuit pump logic function: Heating
circuit pump "OFF"
4
AT > RT
set
+ 2 K
5
AT > RT
set
+ 1 K
6
AT > RT
set
7
to
AT > RT
set
- 1 K
15
AT > RT
set
- 9 K
Coding in the delivered condition
Possible change
Boiler circuit, mixer circuit
A6:36
Extended economy
function
disabled
(only
for weather-compen-
sated control units)
A6:5
to
A6:35
Extended economy func-
tion enabled, i.e. the
burner and heating circuit
pump will be switched
OFF and the mixer
closed at a variable
value, adjustable be-
tween 5 and 35 °C plus
1 °C. This value is based
on the adjusted outside
temperature, comprising
the actual outside tem-
perature and a time con-
stant that takes the
cooling down of an aver-
age building into consid-
eration.
A7:0
Without mixer economy
function (only for weath-
er-compensated control
units)
A7:1
With mixer economy
function (extended heat-
ing circuit pump logic):
Heating circuit pump also
"OFF":
If a mixer has been
closed for longer than
20 min.
Heating pump "ON":
&
If the mixer changes to
control mode
&
If there is a risk of frost
Code 2
(cont.)
64
Coding
5592
817
GB
Содержание VITOPEND 200
Страница 9: ...Installing the boiler and making all connections 9 Installation sequence 5592 817 GB Installation...
Страница 12: ...Opening the control unit casing 12 Installation sequence 5592 817 GB...
Страница 16: ...Fitting the programming unit into the control unit 16 Installation sequence 5592 817 GB...
Страница 17: ...Fitting the front panel 17 Installation sequence 5592 817 GB Installation...
Страница 113: ...Connection and wiring diagram internal connections 113 Designs 5592 817 GB Service...
Страница 119: ...Parts lists cont 119 Parts lists 5592 817 GB Service...
Страница 120: ...Parts lists cont 120 Parts lists 5592 817 GB...
Страница 121: ...Parts lists cont 121 Parts lists 5592 817 GB Service...
Страница 122: ...Parts lists cont 122 Parts lists 5592 817 GB...
Страница 130: ...130 5592 817 GB...
Страница 131: ...131 5592 817 GB...