79
The minimum set boiler water tempera-
ture in case of external demand is selec-
ted in coding address "9b".
Screed drying function
The screed function enables screeds to
be dried. For this, always observe the
details specified by the screed manufac-
turer.
When the screed drying function is acti-
vated, the heating circuit pump of the
mixer circuit is switched ON and the flow
temperature will be held at the selected
profile. After completion (30 days), the
mixer circuit will again be regulated auto-
matically via the set parameters.
Observe EN 1264. The report to be pro-
vided by the heating contractor must
contain the following heat-up details:
■ Heat-up data with respective flow tem-
peratures
■ Max. flow temperature achieved
■ Operating condition and outside tem-
perature during handover
The various temperature profiles are
adjustable via coding address "F1".
The function continues after power fail-
ure or after the control unit has been
switched OFF. "Heating and DHW" will
be started after the screed drying func-
tion has been terminated or if code
"F1:0" is manually adjusted.
Temperature profile 1: (EN 1264-4) code "F1:1"
Flow temperature °C
1
5
10
15
20
25
30
Days
50
40
30
20
10
Temperature profile 2: (ZV parquet and flooring technology) code "F1:2"
Flow temperature °C
Days
50
40
30
20
10
1
5
10
15
20
25
30
Function description
Control functions
(cont.)
5692 774 GB
Содержание Vitoladens 300-C
Страница 88: ...88 Internal extensions H1 PCB A5 and H3 PCB A9 Designs Connection and wiring diagram internal cont 5692 774 GB ...
Страница 92: ...92 206 217 221 205 202 203 204 221 201 214 208 216 215 200 214 Parts lists Parts lists cont 5692 774 GB ...
Страница 95: ...95 308 312 311 310 313 309 306 307 305 309 314 304 Parts lists Parts lists cont 5692 774 GB ...
Страница 96: ...96 100 102 108 111 112 103 109 106 101 Parts lists Parts lists cont 5692 774 GB ...
Страница 103: ...103 5692 774 GB ...