74
Extension kit for heating circuit with mixer
Checking the rotational direction of
the mixer motor
1.
Switch ON/OFF switch
A
at the
extension kit first OFF and then ON
again. The device will carry out the
following self-test:
■ Mixer "Close" (150 s)
■ Pump "ON" (10 s)
■ Mixer "Open" (10 s)
■ Mixer "Close" (10 s)
Then standard control mode
resumes.
2.
Note the rotational direction of the
mixer motor during its self-test.
Then set the mixer manually to
"Open" again.
Note
The flow temperature sensor must
now capture a higher temperature. If
the temperature drops, either the
motor is turning in the wrong direction
or the mixer set is incorrectly fitted.
Mixer installation instructions
Changing the rotational direction of the mixer motor (if required)
Danger
An electric shock can be life-threatening.
Before opening the equipment, switch OFF the ON/OFF switch and mains
voltage, for example at the fuse or the main isolator.
Troubleshooting
Repairs
(cont.)