Coding in the delivered condition
Possible change
User no.
77:1
LON user number
77:2
to
77:99
LON subscriber number,
adjustable from 1 to 99:
1 - 4 = Boiler
5 = Cascade
10 - ... = Vitotronic 200-H
99 = Vitocom
Note
Allocate each number
only once.
DHW priority A1/M2
A2:2
Cylinder priority control
for heating circuit pump
and mixer
A2:0
Without cylinder priority
applicable to heating circuit
pump and mixer
A2:1
Cylinder priority only appli-
cable to mixer
A2:3
to
A2:15
Modulating priority applied
to mixer; i.e. the heating cir-
cuit receives a reduced
amount of heat
Summer econ. A1/M2
A5:5
With heating circuit pump
logic function
A5:0
Without heating circuit
pump logic function
Min. flow temp. A1/M2
C5:20
Electronic minimum flow
temperature limit 20 °C
C5:1
to
C5:127
Minimum limit adjustable
from 1 to 127 °C
Max. flow temp. A1/M2
C6:74
Electronic maximum flow
temperature limit set to
74 °C
C6:1
to
C6:127
Maximum limit adjustable
from 1 to 127 °C
Slope A1/M2
d3:14
Heating curve slope =
1.4
d3:02
to
d3:35
Heating curve slope adjust-
able from 0.2 to 3.5 (see
page 30)
Level A1/M2
d4:0
Heating curve level = 0
d4:–13
to
d4:40
Heating curve level adjust-
able from –13 to 40 (see
page 30)
Codes
Code 1
(cont.)
5692 774 GB
Содержание Vitoladens 300-C
Страница 88: ...88 Internal extensions H1 PCB A5 and H3 PCB A9 Designs Connection and wiring diagram internal cont 5692 774 GB ...
Страница 92: ...92 206 217 221 205 202 203 204 221 201 214 208 216 215 200 214 Parts lists Parts lists cont 5692 774 GB ...
Страница 95: ...95 308 312 311 310 313 309 306 307 305 309 314 304 Parts lists Parts lists cont 5692 774 GB ...
Страница 96: ...96 100 102 108 111 112 103 109 106 101 Parts lists Parts lists cont 5692 774 GB ...
Страница 103: ...103 5692 774 GB ...