Heating program changeover
Code
Heating circuit with mixer M2
91:2
Heating circuit without mixer and heating circuit with mixer
91:3
You can select in which direction the
heating program changes over in coding
address "D5":
Heating program changeover
Code
Changeover towards "Permanently reduced" or "Permanent
standby" mode (subject to the selected set value)
d5:0
Changeover towards "Constant heating mode"
d5:1
The duration of the heating program
changeover can be adjusted in coding
address "F2":
Heating program changeover
Code
No heating program changeover
F2:0
Duration of the heating program changeover 1 to 12 hours
F2:1 to
F2:12
The heating program changeover stays
enabled for as long as the contact
remains closed, but at least as long as
the duration selected in coding address
"F2".
External blocking
The "External blocking" function is con-
nected via input "
aVD
".
In coding address "32" you can select the
influence the "Ext. blocking" signal
should have on the connected circulation
pumps.
External demand
The "External demand" function is con-
nected via input "
aVD
".
In coding address "34" you can select the
influence the "Ext. demand" signal
should have on the connected circulation
pumps.
Function description
Control functions
(cont.)
5692 774 GB
Содержание Vitoladens 300-C
Страница 88: ...88 Internal extensions H1 PCB A5 and H3 PCB A9 Designs Connection and wiring diagram internal cont 5692 774 GB ...
Страница 92: ...92 206 217 221 205 202 203 204 221 201 214 208 216 215 200 214 Parts lists Parts lists cont 5692 774 GB ...
Страница 95: ...95 308 312 311 310 313 309 306 307 305 309 314 304 Parts lists Parts lists cont 5692 774 GB ...
Страница 96: ...96 100 102 108 111 112 103 109 106 101 Parts lists Parts lists cont 5692 774 GB ...
Страница 103: ...103 5692 774 GB ...