32
Changing the slope and level
A
B
Boiler water or flow temperature in °C
90
+20
-20
Outside temperature in °C
3.5
1.4
0.2
A
Changing the slope
B
Changing the level (vertical parallel
offset of the heating curve)
1. Slope:
Change with coding address "d3" in
code 1.
Setting range 2 to 35 (equals slope
0.2 to 3.5).
2. Level:
Change with coding address "d4" in
code 1.
Setting range -13 to +40 K.
Adjusting the set room temperature
Standard room temperature
90
-20
26 + 20
A
C
D
E
B
Example 1: Adjustment of standard room
temperature from 20 to 26 °C
A
Boiler water temperature or flow
temperature in °C
B
Outside temperature in °C
C
Set room temperature in °C
D
Heating circuit pump "OFF"
E
Heating circuit pump "ON"
Press the following keys:
1.
a
"1
r
" flashes.
2.
d
to select heating circuit A1 (heat-
ing circuit without mixer)
or
3.
a
"2
r
" flashes.
4.
d
to select heating circuit with
mixer M2.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5692 774 GB
Содержание Vitoladens 300-C
Страница 88: ...88 Internal extensions H1 PCB A5 and H3 PCB A9 Designs Connection and wiring diagram internal cont 5692 774 GB ...
Страница 92: ...92 206 217 221 205 202 203 204 221 201 214 208 216 215 200 214 Parts lists Parts lists cont 5692 774 GB ...
Страница 95: ...95 308 312 311 310 313 309 306 307 305 309 314 304 Parts lists Parts lists cont 5692 774 GB ...
Страница 96: ...96 100 102 108 111 112 103 109 106 101 Parts lists Parts lists cont 5692 774 GB ...
Страница 103: ...103 5692 774 GB ...