Coding in the delivered condition
Possible change
9C:20
Monitoring LON sub-
scribers
When there is no re-
sponse from a subscri-
ber, values defaulted by
the control unit continue
to be used for a further
20 min. Only then will a
fault message be is-
sued.
9C:0
No monitoring
9C:5
to
9C:60
The time is adjustable
from 5 to 60 min
9F:8
Differential temperature
8 K; only in conjunction
with a heating circuit
with mixer
9F:0
to
9F:40
Differential temperature
adjustable from 0 to 40 K
Boiler circuit, mixer circuit
A0:0
Without remote control
A0:1
With Vitotrol 200 (auto-
matic recognition)
A0:2
With Vitotrol 300 (auto-
matic recognition)
A3:2
Outside temperature
below 1 °C: Heating cir-
cuit pump "ON"
Outside temperature
above 3 °C: Heating cir-
cuit pump "OFF"
Note
When selecting a value
below 1 °C, there is a
risk of pipes outside the
thermal envelope of the
building being damaged
by frost. The standby
mode, in particular,
should be taken into
consideration, e.g. dur-
ing holidays.
A3:-9
to
A3:15
Heating circuit pump
"ON/OFF" (see the fol-
lowing table)
Code 2
(cont.)
77
Coding
5592
883
GB
Service
Содержание VITODENS 343-F WS4A
Страница 105: ...3 Replace the sensor in case of severe deviation Repairs cont 105 Troubleshooting 5592 883 GB Service ...
Страница 131: ...A1 Main PCB A2 Main PCB Connection and wiring diagram internal connections II 131 Designs 5592 883 GB Service ...
Страница 137: ...Parts lists cont 137 Parts lists 5592 883 GB Service ...
Страница 138: ...Parts lists cont 138 Parts lists 5592 883 GB ...
Страница 139: ...Parts lists cont 139 Parts lists 5592 883 GB Service ...
Страница 140: ...Parts lists cont 140 Parts lists 5592 883 GB ...
Страница 141: ...Parts lists cont 141 Parts lists 5592 883 GB Service ...
Страница 142: ...Parts lists cont 142 Parts lists 5592 883 GB ...
Страница 151: ...151 5592 883 GB ...