Cleaning the combustion chamber/heating surfaces and fit-
ting the burner
1.
If required, clean heating
surfaces
A
with a brush or flush
with water.
!
Please note
Scratches on parts that are
in contact with flue gases
can lead to corrosion.
Only use plastic brushes and
NOT wire brushes.
Apply a solvent/potassium-free
cleaning agent if residues remain:
&
Remove soot deposits with alka-
line cleaning agents with addi-
tional surfactants (e.g.
Fauch 600).
&
Remove coatings and surface
discolouration (yellow-brown)
with slightly acidic, chloride-free
cleaning agents based on phos-
phoric acid (e.g. Antox 75 E).
&
Thoroughly flush with water.
Note
Fauch 600 and Antox 75 E are sup-
plied by
Hebro Chemie GmbH
Rostocker Straße 40
D 41199 Mönchengladbach
2.
Install the burner and torque nuts
diagonally with 4 Nm.
3.
Fit the gas supply pipe with a new
gasket.
Further details regarding the individual steps
(cont.)
39
Commissioning, inspection, maintenance
5592
883
GB
Service
Содержание VITODENS 343-F WS4A
Страница 105: ...3 Replace the sensor in case of severe deviation Repairs cont 105 Troubleshooting 5592 883 GB Service ...
Страница 131: ...A1 Main PCB A2 Main PCB Connection and wiring diagram internal connections II 131 Designs 5592 883 GB Service ...
Страница 137: ...Parts lists cont 137 Parts lists 5592 883 GB Service ...
Страница 138: ...Parts lists cont 138 Parts lists 5592 883 GB ...
Страница 139: ...Parts lists cont 139 Parts lists 5592 883 GB Service ...
Страница 140: ...Parts lists cont 140 Parts lists 5592 883 GB ...
Страница 141: ...Parts lists cont 141 Parts lists 5592 883 GB Service ...
Страница 142: ...Parts lists cont 142 Parts lists 5592 883 GB ...
Страница 151: ...151 5592 883 GB ...