Checking and replacing the impressed current anode (if
required)
1.
Check impressed current anode
G
for damage (see page 41).
2.
If required, remove impressed cur-
rent anode
G
from flange lid
E
and fit a new electrode.
3.
Bend impressed current anode
G
in accordance with the pattern of
the old electrode.
Returning the DHW cylinder into use
1.
Insert new gasket
F
under flange
lid
E
(see page 41).
2.
Fit flange lid
E
and tighten the
screws with a maximum torque of
25 Nm.
!
Please note
To safeguard the protective
effect ensure during installa-
tion, that impressed current
anode
G
has no contact
with the internal indirect coil.
After the installation, check
the resistance between
cable
C
and anode con-
nection
D
–
the resistance
must go towards infinity.
3.
Push cable
C
onto anode connec-
tion
D
.
4.
Open the on-site shut-off valve and
check for leaks.
5.
Install thermal insulation hood
B
.
Checking the diaphragm expansion vessel and heating cir-
cuit pressure
Note
Carry out this test on a cold system.
1.
Drain the system or close the cap
valve on the diaphragm expansion
vessel and reduce the pressure
until the pressure gauge indicates
"0".
Further details regarding the individual steps
(cont.)
42
Commissioning, inspection, maintenance
5592
883
GB
Содержание VITODENS 343-F WS4A
Страница 105: ...3 Replace the sensor in case of severe deviation Repairs cont 105 Troubleshooting 5592 883 GB Service ...
Страница 131: ...A1 Main PCB A2 Main PCB Connection and wiring diagram internal connections II 131 Designs 5592 883 GB Service ...
Страница 137: ...Parts lists cont 137 Parts lists 5592 883 GB Service ...
Страница 138: ...Parts lists cont 138 Parts lists 5592 883 GB ...
Страница 139: ...Parts lists cont 139 Parts lists 5592 883 GB Service ...
Страница 140: ...Parts lists cont 140 Parts lists 5592 883 GB ...
Страница 141: ...Parts lists cont 141 Parts lists 5592 883 GB Service ...
Страница 142: ...Parts lists cont 142 Parts lists 5592 883 GB ...
Страница 151: ...151 5592 883 GB ...