Coding in the delivered condition
Possible change
Max. boiler water temp.
06:...
Maximum limit of the
boiler water tempera-
ture, defaulted by the
boiler coding card
06:20
to
06:75
Maximum limit of the boil-
er water temperature
within the ranges de-
faulted by the compact
boiler
Venting/filling
2F:0
Venting program/fill pro-
gram disabled
2F:1
Venting program enabled
2F:2
Fill program enabled
Subscriber no.
77:1
LON subscriber number 77:2
to
77:99
LON subscriber number,
adjustable from 1 to 99:
1-4 = Compact boiler
5 = Never adjust
10 - 98 = Vitotronic 200-H
99 = Vitocom
Note
Allocate each number
only
once.
Summer econ. A1
A5:5
With heating circuit
pump logic function
A5:0
Without heating circuit
pump logic function
Min. flow temp. A1
C5:20
Electronic minimum
flow temperature limit
20 °C
C5:1
to
C5:75
Minimum limit adjustable
from 1 to 75 °C
Max. flow temp. A1
C6:75
Electronic maximum
flow temperature limit
set to 75 °C
C6:10
to
C6:75
Maximum limit adjustable
from 10 to 75 °C
Slope A1
d3:14
Heating curve slope =
1.4
d3:2
to
d3:35
Heating curve slope ad-
justable from 0.2 to 3.5
(see page 54)
Level A1
d4:0
Heating curve level = 0
d4:
–
13
to
d4:40
Heating curve level ad-
justable from
–
13 to 40
(see page 54)
Code 1
(cont.)
67
Coding
5592
883
GB
Service
Содержание VITODENS 343-F WS4A
Страница 105: ...3 Replace the sensor in case of severe deviation Repairs cont 105 Troubleshooting 5592 883 GB Service ...
Страница 131: ...A1 Main PCB A2 Main PCB Connection and wiring diagram internal connections II 131 Designs 5592 883 GB Service ...
Страница 137: ...Parts lists cont 137 Parts lists 5592 883 GB Service ...
Страница 138: ...Parts lists cont 138 Parts lists 5592 883 GB ...
Страница 139: ...Parts lists cont 139 Parts lists 5592 883 GB Service ...
Страница 140: ...Parts lists cont 140 Parts lists 5592 883 GB ...
Страница 141: ...Parts lists cont 141 Parts lists 5592 883 GB Service ...
Страница 142: ...Parts lists cont 142 Parts lists 5592 883 GB ...
Страница 151: ...151 5592 883 GB ...