Setting the maximum output
Note
You can limit the maximum output for
heating operation
. The limit is set via the
modulation range.
1.
Start the compact boiler.
2.
Press
K
and
F
simultaneously
until "100" flashes in the display (=
100 % of rated output) and "Max.
output" and "
A
" appear.
3.
With
a
/
b
select the required
value in % of rated output as maxi-
mum output.
4.
Confirm the set value with
d
.
5.
Record the settings for maximum
output on the additional type plate
included with the "technical docu-
mentation". Affix the additional type
plate next to the original type plate
on top of the compact boiler.
Checking the balanced flue system for soundness (annular
gap check)
A
Combustion air port
For balanced flue systems tested
together with the wall mounted gas
fired boiler, some authorities waive
the requirement for a soundness test
(overpressure test) during commis-
sioning by the flue gas inspector.
We recommend that your heating
engineer carries out a simple sound-
ness test during the commissioning of
your system. For this, it would be suf-
ficient to check the CO
2
or O
2
concen-
tration in the combustion air at the
annular gap of the balanced flue pipe.
Further details regarding the individual steps
(cont.)
35
Commissioning, inspection, maintenance
5592
883
GB
Service
Содержание VITODENS 343-F WS4A
Страница 105: ...3 Replace the sensor in case of severe deviation Repairs cont 105 Troubleshooting 5592 883 GB Service ...
Страница 131: ...A1 Main PCB A2 Main PCB Connection and wiring diagram internal connections II 131 Designs 5592 883 GB Service ...
Страница 137: ...Parts lists cont 137 Parts lists 5592 883 GB Service ...
Страница 138: ...Parts lists cont 138 Parts lists 5592 883 GB ...
Страница 139: ...Parts lists cont 139 Parts lists 5592 883 GB Service ...
Страница 140: ...Parts lists cont 140 Parts lists 5592 883 GB ...
Страница 141: ...Parts lists cont 141 Parts lists 5592 883 GB Service ...
Страница 142: ...Parts lists cont 142 Parts lists 5592 883 GB ...
Страница 151: ...151 5592 883 GB ...