Remote control
DIP switch setting
The remote control affects the heating
circuit without mixer A1
The remote control affects the heating
circuit with mixer M2
When connecting a separate room
temperature sensor, set DIP switch "3"
to "ON".
Electronic combustion control unit
The electronic combustion control unit
utilises the physical correlation
between the size of the ionisation cur-
rent and the air factor
λ
. In case of air
factor 1, the maximum ionisation cur-
rent results for all gas qualities.
The ionisation signal is evaluated by
the combustion control unit, and the
air factor is adjusted to between
λ
=1.24 and 1.44. This range provides
for an optimum combustion quality.
Thereafter, the electronic gas valve
regulates the required gas volume
subject to the prevailing gas quality.
To check the combustion quality, the
CO
2
content or the O
2
content of the
flue gas is measured. The actual
values enable the prevailing air factor
to be determined. The relationship
between the CO
2
or O
2
content and
air factor
λ
is illustrated in the follow-
ing table.
Remote control DIP switches
(cont.)
127
Function description
5592
883
GB
Service
Содержание VITODENS 343-F WS4A
Страница 105: ...3 Replace the sensor in case of severe deviation Repairs cont 105 Troubleshooting 5592 883 GB Service ...
Страница 131: ...A1 Main PCB A2 Main PCB Connection and wiring diagram internal connections II 131 Designs 5592 883 GB Service ...
Страница 137: ...Parts lists cont 137 Parts lists 5592 883 GB Service ...
Страница 138: ...Parts lists cont 138 Parts lists 5592 883 GB ...
Страница 139: ...Parts lists cont 139 Parts lists 5592 883 GB Service ...
Страница 140: ...Parts lists cont 140 Parts lists 5592 883 GB ...
Страница 141: ...Parts lists cont 141 Parts lists 5592 883 GB Service ...
Страница 142: ...Parts lists cont 142 Parts lists 5592 883 GB ...
Страница 151: ...151 5592 883 GB ...