Yes
Ignition
No
Fault F4
Check the ignition
module (control
voltage 230 V
across plugs
"X2.1" and
"X2.2")
Yes
Gas train opens
No
Fault F4
Check the gas
train (control vol-
tage 230 V);
check the gas
supply pressure
Yes
Ionisation cur-
rent builds
Symbol
A
No
Fault F4
Check the ionisa-
tion electrode ad-
justment and the
gas pipe for air-
locks
Yes
Burner in opera-
tion
No
Stops below the
set boiler water
temperature and
restarts immedi-
ately
Check the flue
gas system for
soundness (flue
gas recirculation),
check the gas
flow pressure
Yes
Automatic cali-
bration of the
combustion con-
trol unit
No
Fault Eb
Check the con-
necting cable and
the ionisation
electrode,
check the flue gas
system (flue gas
recirculation)
Further details regarding the individual steps
(cont.)
32
Commissioning, inspection, maintenance
5592
883
GB
Содержание VITODENS 343-F WS4A
Страница 105: ...3 Replace the sensor in case of severe deviation Repairs cont 105 Troubleshooting 5592 883 GB Service ...
Страница 131: ...A1 Main PCB A2 Main PCB Connection and wiring diagram internal connections II 131 Designs 5592 883 GB Service ...
Страница 137: ...Parts lists cont 137 Parts lists 5592 883 GB Service ...
Страница 138: ...Parts lists cont 138 Parts lists 5592 883 GB ...
Страница 139: ...Parts lists cont 139 Parts lists 5592 883 GB Service ...
Страница 140: ...Parts lists cont 140 Parts lists 5592 883 GB ...
Страница 141: ...Parts lists cont 141 Parts lists 5592 883 GB Service ...
Страница 142: ...Parts lists cont 142 Parts lists 5592 883 GB ...
Страница 151: ...151 5592 883 GB ...