Fault code
in the dis-
play
Const.
Weat-
h.
comp.
System
character-
istics
Cause
Remedy
dd
X
Room temperature
sensor heating cir-
cuit A1 lead break
Check the
room tem-
perature sen-
sor - heating
circuit A1
dE
X
Heating circuit M2
room temperature
sensor lead break
Check the
room tem-
perature sen-
sor - heating
circuit M2
E4
X
X
Burner
blocked
Fault - supply vol-
tage
Replace con-
trol unit
E5
X
X
Burner
blocked
Internal error
Check the
ionisation
electrode and
leads. Check
flue gas sys-
tem for
soundness.
Press
E
.
E6
X
X
Burner in
fault state
Flue gas/air supply
system blocked
Check the
flue gas/air
supply sys-
tem. Check
the differen-
tial pressure
sensor.
Press
E
.
F0
X
X
Burner
blocked
Internal error
Replace con-
trol unit
F1
X
X
Burner in
fault state
Flue gas tempera-
ture limiter has
responded
Check the
heating sys-
tem water
level. Vent
the heating
system.
Press reset
E
no sooner
than after
20 minutes.
Checking and acknowledging faults
(cont.)
80
Troubleshooting
56
92
548
GB
Содержание VITODENS 333
Страница 114: ...Parts lists cont 114 Parts lists 5692 548 GB ...
Страница 115: ...Parts lists cont 115 Parts lists 5692 548 GB ...
Страница 116: ...Parts lists cont 116 Parts lists 5692 548 GB ...
Страница 117: ...Parts lists cont 117 Parts lists 5692 548 GB ...
Страница 118: ...Parts lists cont 118 Parts lists 5692 548 GB ...
Страница 119: ...Parts lists cont 119 Parts lists 5692 548 GB ...
Страница 131: ...131 5692 548 GB ...