Boiler control
unit
Vitotronic 050
Vitotronic 050
Vitocom
Sent time via LON
Code 7b: 1
Time received via
LON
Set
code 81: 3
Time received via
LON
Set
code 81: 3
Time received
via LON
Transmit outside
temperature via
LON
Set
code 97: 2
Outside tempera-
ture is received via
LON
Set
code 97: 1
Outside tempera-
ture is received via
LON
Set
code 97: 1
—
Implementing a user check (in conjunction with the LON sys-
tem)
The communication with the system devices connected to the fault manager is
tested with a user check.
Preconditions:
&
The control unit must be encoded as fault manager (code 79:1).
&
The LON user number must be encoded in all control units (see page 32).
&
The fault manager LON user list must be up to date (see page 32).
A
Consecutive list number
B
User number
1.
Press
L
and
d
simultaneously
for approx. 2 seconds. User check
initiated.
2.
Select the required user with
a
and
b
.
3.
Activate checking with
d
.
Check
flashes until its completion.
The display and all key illumina-
tions of the selected user flash for
approx. 60 seconds.
&
Check OK
flashes during com-
munication between both
devices.
&
Check not OK
flashes if there is
no communication between both
devices. Check LON connection.
4.
For checking further users, proceed
as for items 2 and 3.
Further details regarding the individual steps
(cont.)
33
Initial start-up, inspection, maintenance
56
92
548
GB
Содержание VITODENS 333
Страница 114: ...Parts lists cont 114 Parts lists 5692 548 GB ...
Страница 115: ...Parts lists cont 115 Parts lists 5692 548 GB ...
Страница 116: ...Parts lists cont 116 Parts lists 5692 548 GB ...
Страница 117: ...Parts lists cont 117 Parts lists 5692 548 GB ...
Страница 118: ...Parts lists cont 118 Parts lists 5692 548 GB ...
Страница 119: ...Parts lists cont 119 Parts lists 5692 548 GB ...
Страница 131: ...131 5692 548 GB ...