Example 1: Modifying the standard
room temperature from 20 °C to 26 °C
A
Boiler water or flow temperature in
°C
B
Outside temperature in °C
C
Set room temperature in °C
D
Heating circuit pump OFF
E
Heating circuit pump ON
2.
Adjust the set day temperature with
rotary selector
ts
.
The value will be automatically
adopted after approx. 2 seconds.
Accordingly, the heating curve is
adjusted along set room tempera-
ture axis
C
, which results in modi-
fied start/shutdown characteristics
of the heating circuit pumps, if the
heating circuit pump logic is acti-
vated.
Reduced room temperature:
1.
For two heating circuits
–
select
heating circuit:
&
Press
a
.
1
r
flashes on the display.
&
Select heating circuit A1 (heating
circuit without mixer):
Press
d
.
&
Select heating circuit M2 (heating
circuit with mixer):
–
Press
a
.
–
2
r
flashes on the display.
–
Press
d
.
Further details regarding the individual steps
(cont.)
36
Initial start-up, inspection, maintenance
56
92
548
GB