Coding in
the as
delivered
condition
Address:
value
Function mode
Coding
change
Address:
value
Possible change
91:0
*
1
No external operating
mode changeover via
external extension
91:1
External heating program
changeover applies to
heating circuit without
mixer
91:2
External heating program
changeover applies to
heating circuit with mixer
91:3
External heating program
changeover applies to
heating circuit without
mixer and heating circuit
with mixer
95:0
Without Vitocom 100
communication inter-
face
95:1
With Vitocom 100 com-
munication interface;
automatic recognition
97:0
*
1
The outside tempera-
ture of the sensor con-
nected to the control
unit is utilised internally
97:1
Outside temperature is
adopted by the LON BUS
97:2
The outside temperature
of the sensor connected
to the control unit will be
utilised internally and
transmitted via LON BUS
to any connected Vitotro-
nic 050.
98:1
Viessmann system
numbers (in conjunction
with monitoring of sev-
eral systems via Vito-
com 300)
98:1
to
98:5
System number adjusta-
ble from 1 to 5
9b:0
No minimum set boiler
water temperature in
case of external
demand
9b:1
to
9b:127
Set temperature adjusta-
ble from 1 to 127 °C
Code 2
(cont.)
51
Coding
56
92
548
GB
*1
Only for weather-compensated control unit.
Содержание VITODENS 333
Страница 114: ...Parts lists cont 114 Parts lists 5692 548 GB ...
Страница 115: ...Parts lists cont 115 Parts lists 5692 548 GB ...
Страница 116: ...Parts lists cont 116 Parts lists 5692 548 GB ...
Страница 117: ...Parts lists cont 117 Parts lists 5692 548 GB ...
Страница 118: ...Parts lists cont 118 Parts lists 5692 548 GB ...
Страница 119: ...Parts lists cont 119 Parts lists 5692 548 GB ...
Страница 131: ...131 5692 548 GB ...