Function sequence and possible faults
Display screen
Measures
Control unit is-
sues heat de-
mand
No
Increase set
value and ensure
heat is drawn off
Yes
Fan starts
No
After approx. 51 s
fault F5/F9
Check fan cables
and plug-in con-
nectors
Yes
Differential pres-
sure sensor en-
ables start
(0.75 V across
terminals "X8.5"
and "X8.6")
No
After approx. 51 s
fault E6/F5
Check fan cables
and plug-in con-
nectors, check
fan
Yes
Ignition
No
Fault F4
Check ignition
module (control
voltage 230 V
across plugs
"X2.1" and
"X2.2")
Yes
Gas train opens
No
Fault F4
Check the gas
train (control vol-
tage 230 V);
check the gas
supply pressure
Further details regarding the individual steps
(cont.)
13
Commissioning, inspection, maintenance
5692
731
GB